Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1Dsl-PS 2-Dsl-PS 3-87-PS 4-91-PS <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 73 1/2" 73 1/2" 73 1/2" 75" <br /> Sump Bottom to Top of 21" 22" 19" 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:32 12:37 12:42 12:47 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 1:02 1:07 1:12 1:17 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 5-87-Siph-PS 6-TLM-1 7-TLM-2 8-TLM-3 <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 75" 74 1/2" 74 1/2" 74" <br /> Sump Bottom to Top of No Piping No Piping No Piping No Piping <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:52 12:57 1:32 1:37 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 1:22 1:27 2:02 2:07 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 9 <br />