Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 3&4 UDC 5&6 UDC 7&8 UDC 9&10 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 30" 30" 30" 30" <br /> Sump Bottom to Top of 10" 10" 10" 10" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:26 12:37 12:42 12:47 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:56 1:07 1:12 1:17 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 11&12 UDC 13&14 UDC 15&16 UDC 17&18 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 30" 30" 30" 30" <br /> Sump Bottom to Top of 10" 10" 10" 10" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:52 12:57 9:16 11:09 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 1:22 1:27 9:46 11:39 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 6 of 9 <br />