Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />October 17, 2023 <br /> Facility Address: <br /> 2758 W Kettleman Ln, Lodi <br /> Facility Name: <br /> Sunwest Chevron <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 301 HSC 25292.1(a) Failure to operate UST system to prevent unauthorized releases including leaks, spills and overfills. <br />OBSERVATION: Per work order #16693 approximately 2 cups of “pink” brine was added to the diesel STP annular. <br />The manufacturer of the diesel tank is Containment Solutions, Inc. (CSI) and contains green/blue colored brine. <br />REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br />releases, including spills and overfills. <br />CORRECTIVE ACTION: Immediately verify the manufacturer of the brine that has been added to the diesel tank. <br />This is a Class II violation. <br /> 302 CCR 2630(d), 2641(a) Leak detection equipment not installed/maintained/located to detect leaks at earliest <br />opportunity. <br />OBSERVATION: Upon arrival the S17 vacuum sensor was found to be in alarm and actions have not been taken to <br />address the alarm. <br />REGULATION GUIDANCE: All monitoring equipment shall be maintained to be able to detect a leak at the earliest <br />possible opportunity. <br />CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to address the <br />alarm under permit and inspection of the EHD. <br />This is a repeat violation, Class II. <br /> 304 CCR 2631(a); HSC 25290.1(c) Failure to construct, operate, and maintain primary containment as product-tight. <br />OBSERVATION: Liquid was observed in UDC 5/6, 7/8, 11/12, & 13/14, indicating a leak in the primary containment. <br />REGULATION GUIDANCE: All primary containment for the UST system must be product tight. <br />CORRECTIVE ACTION: Immediately have a properly licensed, trained, and certified contractor repair or replace the <br />failed component(s), under permit and inspection of the EHD if necessary. <br />This is a repeat violation, Class II. <br />FA0023733 PR0541416 SC001 10/17/2023 <br />EHD 23-01 Rev. 12/06/2021 Underground Storage Tank Program OIRPage 9 of 11 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD