Laserfiche WebLink
NEW SERVICE <br />MOUNTING: SURFACE PANEL: A- NEW MAIN: 400A <br />GENERAL NOTES <br />SINGLE LINE DIAGRAM <br />120/240 VOLT 30 PHASE 4 WIRE BUS: 400A <br />331-21E1 <br />1. ALL WIRING SHALL BE 3-12GA THWN CU-W/ 1/2" EMT UNLESS OTHERWISE NOTED. <br />NEW 4" 0 CONDUIT WITH <br />2. ALL ELECTRICAL WIRING AND BONDING SHALL MEET C.E.C, 2019 <br />(E) POWER POLE NEW OVERHEAD SERVICE <br />NEW COMMERCIAL METERING SWITCHBOARD <br />NEMA 3R, W/ UNDERGROUND PULL SECTION <br />NEW OVERHEAD SECONDARY 400AMP/120V/240V/30 <br />F_ 1Qjq <br />3. ALL RECEPTACLES SHALL BE +15"A.F.F. UNLESS OTHERWISE NOTED, <br />ALL CONTROLS SHALL BE MIN. OF +36" A.F.F. & MAX. OF 48" A.F.F. <br />4. ALL EQUIPMENT GROUNDING SHALL CONFORM TO ARTICLE 250 OF THE CALIFORNIA <br />ELECTRIC CODE, LATEST EDITION. <br />5. PANEL BOARD CIRCUIT BREAKERS USED AS SWITCHES MUST BE APPROVED FOR <br />LOCATION <br />WATTAGEF- <br />= <br />U <br />J <br />W <br />tY <br />U <br />Y <br />m <br />U <br />U <br />U <br />Of <br />U <br />Y <br />m <br />U <br />W <br />�' <br />= <br />C7 <br />J <br />WATTAGE <br />LOCATION <br />Qjg <br />OC <br />OA <br />f71B <br />fDC <br />MSB-400AMP/120V/240V/30/4W/ BUS <br />LOCATION LANDING LUGS I M I <br />SUCH DUTY AND BE OF THE "SWD" TYPE PER SECTION 240-83 (d) OF THE N.E.C. <br />6. PROVIDE PARITY SIZED GREEN GROUND WIRE IN ALL CONDUITS/BRANCH CIRCUIT <br />HOMERUNS. <br />7. ALL CONDUIT PENETRATIONS THROUGH FIRE-RATED WALLS AND FLOORS SHALL <br />PLUGS <br />480 <br />20 <br />1 <br />1 <br />2 <br />20 <br />1 <br />1440 <br />MERCHANDISER REF <br />2.4 A 120 V & <br />FOOD PREP. REF. <br />6.5 A 120 K <br />780 <br />20 <br />1 <br />3 <br />4 <br />20 <br />1 <br />1080 <br />WALK-IN FAN COIL <br />AMPS. 120V <br />CHEF BASE REF. <br />8.1 A BA M <br />972 <br />20 <br />1 <br />5 <br />6 <br />20 <br />1 <br />960 <br />BAKERY A ER ERX Y DISPLAY <br />UNDER COUNTER REV <br />3.2 A 120 N <br />384 <br />1 <br />7 <br />8 <br />20 <br />1 <br />180 <br />PLUG <br />NEW METER-TYP. I I I <br />BE SEALED TO MAINTAIN FIRE-SEPARATION RATING, USE 3M FIRE BARRIER <br />FS-195 WRAP/STRIP AT PVC PIPE PENETRATION THRU RATED WALLS. OR EQUAL <br />PRODUCTS. <br />AIR CURTAIN <br />2.4 A 12 <br />288 <br />20 <br />1 <br />9 <br />10 <br />20 <br />1 <br />1800 <br />BAKERY OVEN <br />15 A 120 BA <br />HOT FOOD WELL <br />18.3 A 240 U <br />2199 <br />30 <br />2 <br />11 <br />12 <br />20 <br />2 <br />816 <br />BAKERY OVEN <br />6.8 A 24010 BA <br />400l3P <br />- I <br />8. DO NOT INSTALL ANY OUTLETS BACK TO BACK IN STUD WALLS. <br />9. UNLESS OTHERWISE NOTED, WHERE TWO SWITCHES CONTROL THE LIGHTING <br />FIXTURES IN A ROOM, CONNECT BALLASTS AND FIXTURES SO THAT ONE SWITCH <br />CONTROLS THE OUTSIDE LAMPS AND THE OTHER SWITCH CONTROLS THE CENTER <br />LAMP(S). <br />2199 <br />13 <br />14 <br />816 <br />WALK-IN FAN COIL <br />288 <br />20 1 <br />15 <br />16 <br />20 1 <br />1800 <br />151 MIXER <br />10 BB <br />GAS SOLENOID <br />180 <br />20 1 <br />17 <br />18 <br />40 <br />2800 <br />WAL 240,30 L. COMF. <br />35 <br />f 16.6 <br />10. DRAWINGS INDICATE THE LOCATION OF DEVICES, FIXTURES AND EQUIPMENT AND <br />EXHAUST FAN #1 <br />528 <br />19 <br />20 <br />2800 <br />THE CIRCUIT NUMBER AND PANEL DESIGNATION WHICH SUPPLIES THEM. ELECTRICAL <br />AMPS, 240V <br />528 <br />tV3 <br />21 <br />22 <br />3 <br />2800 <br />CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CONNECTING ALL <br />528 <br />23 <br />24 <br />40 <br />3 <br />2800 <br />WAL35 K-INCOOL. COMF. <br />30 <br />~ O <br />Z) Z <br />GROUND PER N.E.C. p <br />ART.250 Z = p <br />O Z <br />LIFER GROUND, 20-L OF #4 U (1) 2" EMT CONDUIT <br />BARE CU IN BOTTOM N CONC. ~ O <br />U 4 3/O THWN CU. <br />FOOTING, ENCASED IN 3" OF p w o N () <br />CONC. z 'v & 1#6 CU. GND. <br />v <br />O <br />O PNL PNL <br />A B <br />3/4" C, 1-#2 CU BOND TO MAIN GAS & <br />METALLIC COLD WATER PIPE WITHIN <br />BUILDING PER ART 250-66 <br />ELECTRICAL DEVICES TO CIRCUITS INDICATED ON THE DRAWINGS. <br />11. USE 3M FIRE BARRIER CP 25 CAULK AT STEEL PIPE PENETRATION TRU RATED <br />WALLS, OR EQUAL PRODUCT. <br />12. PROVIDE MIN. OF 24" HORIZONTAL SEPARATION, IN BETWEEN ELECTRICAL BOXES <br />LOCATED ON OPPOSITE SIDE OF WALLS PER CBC SEC. 714.3.2 <br />13. PENETRATION ON EITHER SIDE OF RATED CORRIDOR WALLS SHALL NOT <br />EXCEED 18" S. IN. PER PENETRATION. <br />14. ALL EXTERIOR LIGHTS SHALL HAVE PHOTO CELL CONTROL. <br />15. TSTAT SHALL BE MOUNTED 40" TO 48" A.F.F. <br />16. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE <br />UNDERWRITTERS' LABORATORIES, INC. SHALL MEET THEIR REQUIREMENTS AND <br />SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED <br />LABEL MSERVICE IS REGULARLY FURNISHED BY THAT AGENCY. <br />MUA <br />852 <br />20 <br />3 <br />25 <br />26 <br />2800 <br />11.9 AMPS, 240V <br />952 <br />27 <br />28 <br />2800 <br />952 <br />29 <br />30 <br />40 <br />3 <br />2800 <br />WALK-IN FREZ.COM <br />35 A 240 30 <br />EXHAUST FAN #2 <br />528 <br />31 <br />32 <br />2800 <br />6.6 AMPS, 240V <br />528 <br />AA3 <br />33 <br />34 <br />2800 <br />528 <br />35 <br />36 <br />20 1 <br />180 <br />PLUG - ROOF <br />MERCHANDISER.COM <br />30 A 240.30 <br />2400 <br />40 <br />37 <br />38 <br />00 <br />13,044 <br />SUB-PANEL B <br />2400 <br />39 <br />40 <br />9600 <br />2400 <br />41 <br />42 <br />13,496 <br />17. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE <br />WATTS: OA= 35,639 OB= 33,579 OB= 22,408 <br />SIZE NAD LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE. <br />1/2"x8'L ROD ART 250-83,84 <br />CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS <br />TOTAL WATTS: = 92,626 AMPS: = 381.7 A <br />AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE <br />RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID <br />F.L.A. @ 125% CONT. LOAD - <br />INTERFERENCE WITH OTHER TRADES. <br />F.L.A. @ 125% LARGEST EQUIPMENT - 390.4 A <br />II& ALL LUMINARIES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER <br />1. VERIFY SHORT CIRCUIT AMPRAGE KAIC RATING WITH MID BEFORE INSTALLATION. <br />TO THE CALIFORNIA ENERGEY COMMISSION. ALL FLUORESCENT FIXTURES TO BE <br />2. VERIFY DISC. SWITCH FOR EQUIP. BEFORE INSTALLATION. <br />LAMPED WITH F032, T8, 3500K LAMPS OR APPROVED EQUAL, AND HAVE AN <br />ENERGY SAVING W SOUND RATING ELECTRONIC BALLAST OR APPROVED EQUAL <br />UNLESS OTHERWISE SHOWN. ALL H.I.D. LIGHT FIXTURES SHALL HAVE HIGH <br />POWER FACTOR BALLASTS. <br />19. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. <br />20. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE <br />INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY <br />MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT <br />MOUNTING: SURFACE PANEL: g- NEW MAIN: 200 q <br />120/240 VOLT 30 PHASE 4 WIRE BUS: 200 q <br />LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES, <br />ROADWAYS, WALKS, CURBS, WALLS, EXISTING UNDERGROUND INSTALLATIONS <br />TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. <br />21. CONNECT T-BAR DROP-IN FIXTURES AT DIAGNOAL CORNERS DIRECTLY TO STRUCTURE <br />OVERHEAD USING MINIMUM #12 WIRE. CLIPS ARE NOT SUITABLE IN SEISMIC ZONE #4. <br />LOCATION <br />WATTAGEWATTAGE <br />2 <br />(7 <br />J <br />U <br />W <br />U <br />Y <br />00 <br />U <br />U <br />U <br />U <br />or <br />Y0 <br />m <br />U <br />2 <br />U <br />W <br />= <br />C9 <br />LOCATION <br />22. SEPARATE PERMIT REQUIRED FOR SIGNS. <br />23. ALL EQUIPMENT SHALL BE HARD WIRED UNLESS SUPPLIED WITH AN APPROVED FACTORY <br />INSTALLED CORD AND MALE CORD END. <br />OA <br />OB <br />OC <br />OA <br />OB <br />0C <br />(E) OVER HEAD SECONDARY (E) BUILDING ELECTRICAL SERVICE PANEL <br />600AMP/120V/240V/30, 4W BUS BARS - <br />- - <br />M M 1 <br />(E) TYP. METER M <br />PROVIDE MINIMUM LIG14TING AS FOLLOWS: <br />1- WALK-IN REFRIGERATION UNIT ( 10 FOOT CANDLES AT 30 INCHES ABOVE THE FLOOR) <br />2- DRY FOOD STORAGE AREA ( 10 FOOT CANDLES AT 30 INCHES ABOVE THE FLOOR) <br />3- SELF SERVICE FOOD (20 FOOT CANDLES MINIMUM) <br />4- PRODUCE OR PREPACKED FOOD (20 FOOT CANDLES MINIMUM) <br />5- INSIDE OF REACHING-IN OR UNDER-COUNTER REFRIGERATORS (20 FOOT CANDLES MINIMUM) <br />6- HAND WASHING, WARE WASHING AND EQUIPMENT AND UTENSIL STORAGE AND TOILET ROOMS <br />(20 FOOT CANDLES MINIMUM AT 30 INCHES ABOVE THE FLOOR) <br />7- FOOD EMPLOYEE IS WORKING WITH FOOD OR WORKING WITH UTENSILS OR EQUIPMENT SUCH <br />AS KNIVES, SLICERS, GRINDERS, OR SAWS WHERE EMPLOYEE SAFETY IS A FACTOR <br />MEAT GRINDER <br />8.9 A 240 10 <br />1068 <br />20 <br />2 <br />1 <br />2 <br />20 <br />1 <br />612 <br />LIGHTS <br />1068 <br />3 <br />4 <br />20 1 <br />240 <br />LIGHTS <br />MEAT GRINDER <br />8.9 A 240 10 <br />1068 <br />20 <br />2 <br />5 <br />6 <br />20 <br />1 <br />80 <br />LIGHTS <br />1068 <br />7 <br />8 <br />MEAT GRINDER <br />8.9 A 240 10 <br />1068 <br />20 <br />9 <br />10 <br />10682 <br />11 <br />12 <br />13 <br />14 <br />(50 FOOD CANDLES MINIMUM) <br />15 <br />16 <br />17 <br />18 <br />c600/3PI ( <br />C200/1 P c 200/3P c 200/3P 200/1 P b 100/1 P <br />RACE WAY EXPOSED OR CONCEALED <br />19 <br />20 <br />- - _ <br />RACE WAY INSTALLED BELOW FLOOR -PVC <br />2 PROVIDE 3" CONCRETE ALL AROUND RACEWAY <br />21 <br />22 <br />23 <br />24 <br />(E) (E) (E) (E) (E) <br />. O LIGHT FIXTURE: CONNECT TO BRANCH CIRCUIT SHOWN (e.g. CIRCUIT 2) <br />25 <br />26 <br />40 <br />2400 <br />MERCHANDISER.COM <br />30 A 240,30 <br />PNL PNL PNL PNL PNL <br />L- (A) (B) (C) (A) (A) <br />SUITE 441 SUITE 441 SUITE 441 SUITE 447 FL SECOND <br />ROOF AC FLOOR <br />RESIDENCE <br />27 <br />28 <br />3 <br />2400 <br />a <br />AO SWITCHING <br />WALL LIGHT SWITCH, SINGLE POLE; (N) BOX CENTERLINE MOUNTING HEIGHT 45" A.F.F. <br />29 <br />30 <br />2400 <br />31 <br />32 <br />40 <br />2400 <br />MERCHANDISER,240.3.COM <br />30 A 240 30 <br />33 <br />34 <br />2400 <br />GROUND PER N.E.C. <br />ART.250 <br />3 <br />OS <br />WALL OCCUPANCY SENSOR: BOX CENTERLINE MOUNTING HEIGHT 45" A.F.F. <br />D <br />DIMMER CONTROL: LEVITON IP710-DLX, WHITE, SINGLE POLE, BOX CENTERLINE <br />35 <br />36 <br />2400 <br />MERCHANDISER.COM <br />30 A. 24030 V <br />.2400 <br />40 <br />2400 <br />MERCHANDISER. COMF. <br />30 A 240.30 <br />2400 <br />LL11 <br />2400 <br />MOUNTING HEIGHT 45" A.F.F. <br />(E) LIFER GROUND, 20'L OF 3/0 <br />PER CEC 250.50(C) <br />33 <br />{�T <br />b TWIST TIMER; 15 MINUTE, NO HOLD, INTERMATIC FF15MC; BOX MOUNTING HEIGHT 45" A.F.F. <br />62 RECEPTACLE OUTLET; DUPLEX; NEMA CONFIGURATION AND RATING 5-20 (2 POLE, 3 WIRE, <br />2400 <br />+_v <br />2400 <br />WATTS: OA= 13,496 OB= 13,044 OO1B= 9,600 <br />20A, 120V) OUTLET BOX CENTERLINE MOUNTING HEIGHT 18" A.F.F.; CONNECT TO BRANCH <br />TOTAL WATTS: = 36,140 AMPS: =150.6 A1, <br />(E) BOND TO MAIN GAS &+48 <br />METALLIC COLD WATER PIPE WITHIN <br />BUILDING PER ART 250-104(B) <br />CIRCUIT SHOWN (e.g. CIRCUIT 2) <br />SAME; EXCEPT HEIGHT A.F.F. SHOWN <br />d GFCISAME; EXCEPT CLASS A GFCI <br />F.L.A. @ 125% CONT. LOAD-31.6 <br />F.L.A. @ 125% LARGEST EQUIPMENT - 158.1 <br />(E) 1/2"x8'L ROD - <br />6 WP SAME, EXCEPT WATER PROOF <br />QUADRUPLEX RECEPTACLE OUTLET (TWO DUPLEX) <br />CEILING MOUNTED SHOW WINDOW RECEPTACLE OUTLETS <br />® FLOOR MOUNTED RECEPTACLE OUTLET; DUPLEX; <br />I ❑ DISCONNECT SWITCH <br />JD JUNCTION BOX <br />TELEPHONE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET <br />EXCEPT WHERE SHOWN <br />DATA / TELEPHONE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET <br />EXCEPT WHERE SHOWN <br />N DATA / TV CABLE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET EXCE <br />WHERE SHOWN <br />-> DUAL HDMI OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET EXCEPT <br />WHERE SHOWN <br />EXISTING ELECTRICAL SERVICE <br />SINGLE LINE DIAGRAM <br />2 3 0 1 Coffee Road #B ♦ Modesto, CA 95355 <br />Phone: 209 - 408-0674 # edmond@etjarchitect.com <br />ARCHITECT: <br />THE DRAWINGS, SPECIFICATIONS, DESIGN AND IDEAS <br />DESCRIBED HEREIN SHALL REMAIN THE PROPERTY OF <br />THE ARCHITECT AND NO PART THEREOF CAN BE COPIED, <br />DUPLICATED, DISCLOSED TO OTHERS OR USED IN <br />CONNECTION WITH ANY WORK OR PROJECT OTHER THAN <br />THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN <br />PREPARED AND DEVELOPED WITHOUT EXPRESS WRITTEN <br />PERMISSION OF THE ARCHITECT. <br />EDMOND T. JACOBS ARCHITECT COPYRIGHT 2022 <br />CONSULTANT <br />PROJECTADDRESS: <br />MANTECA FOOD <br />TENANT IMPROVEMENT <br />KITCHEN <br />& MEAT AREA <br />REMODEL <br />441 N. MAIN ST. <br />MANTECA, CA 95336 <br />CLIENT: <br />MR. EMAD MOHSEN <br />447 N. MAIN STREET <br />MANTECA, CA 95336 <br />DATE: <br />MARCH 11, 2022 <br />DRAWN: <br />ETJ <br />FILE: <br />331-21E1 <br />PROJECT NO: 329-21 <br />PERMIT NO: <br />DESCRIPTION: <br />NOTES / SINGLE <br />LINE DIAGRAM <br />SCHEDULE <br />SHEET NO. <br />F <br />E-1 <br />