NEW SERVICE
<br />MOUNTING: SURFACE PANEL: A- NEW MAIN: 400A
<br />GENERAL NOTES
<br />SINGLE LINE DIAGRAM
<br />120/240 VOLT 30 PHASE 4 WIRE BUS: 400A
<br />331-21E1
<br />1. ALL WIRING SHALL BE 3-12GA THWN CU-W/ 1/2" EMT UNLESS OTHERWISE NOTED.
<br />NEW 4" 0 CONDUIT WITH
<br />2. ALL ELECTRICAL WIRING AND BONDING SHALL MEET C.E.C, 2019
<br />(E) POWER POLE NEW OVERHEAD SERVICE
<br />NEW COMMERCIAL METERING SWITCHBOARD
<br />NEMA 3R, W/ UNDERGROUND PULL SECTION
<br />NEW OVERHEAD SECONDARY 400AMP/120V/240V/30
<br />F_ 1Qjq
<br />3. ALL RECEPTACLES SHALL BE +15"A.F.F. UNLESS OTHERWISE NOTED,
<br />ALL CONTROLS SHALL BE MIN. OF +36" A.F.F. & MAX. OF 48" A.F.F.
<br />4. ALL EQUIPMENT GROUNDING SHALL CONFORM TO ARTICLE 250 OF THE CALIFORNIA
<br />ELECTRIC CODE, LATEST EDITION.
<br />5. PANEL BOARD CIRCUIT BREAKERS USED AS SWITCHES MUST BE APPROVED FOR
<br />LOCATION
<br />WATTAGEF-
<br />=
<br />U
<br />J
<br />W
<br />tY
<br />U
<br />Y
<br />m
<br />U
<br />U
<br />U
<br />Of
<br />U
<br />Y
<br />m
<br />U
<br />W
<br />�'
<br />=
<br />C7
<br />J
<br />WATTAGE
<br />LOCATION
<br />Qjg
<br />OC
<br />OA
<br />f71B
<br />fDC
<br />MSB-400AMP/120V/240V/30/4W/ BUS
<br />LOCATION LANDING LUGS I M I
<br />SUCH DUTY AND BE OF THE "SWD" TYPE PER SECTION 240-83 (d) OF THE N.E.C.
<br />6. PROVIDE PARITY SIZED GREEN GROUND WIRE IN ALL CONDUITS/BRANCH CIRCUIT
<br />HOMERUNS.
<br />7. ALL CONDUIT PENETRATIONS THROUGH FIRE-RATED WALLS AND FLOORS SHALL
<br />PLUGS
<br />480
<br />20
<br />1
<br />1
<br />2
<br />20
<br />1
<br />1440
<br />MERCHANDISER REF
<br />2.4 A 120 V &
<br />FOOD PREP. REF.
<br />6.5 A 120 K
<br />780
<br />20
<br />1
<br />3
<br />4
<br />20
<br />1
<br />1080
<br />WALK-IN FAN COIL
<br />AMPS. 120V
<br />CHEF BASE REF.
<br />8.1 A BA M
<br />972
<br />20
<br />1
<br />5
<br />6
<br />20
<br />1
<br />960
<br />BAKERY A ER ERX Y DISPLAY
<br />UNDER COUNTER REV
<br />3.2 A 120 N
<br />384
<br />1
<br />7
<br />8
<br />20
<br />1
<br />180
<br />PLUG
<br />NEW METER-TYP. I I I
<br />BE SEALED TO MAINTAIN FIRE-SEPARATION RATING, USE 3M FIRE BARRIER
<br />FS-195 WRAP/STRIP AT PVC PIPE PENETRATION THRU RATED WALLS. OR EQUAL
<br />PRODUCTS.
<br />AIR CURTAIN
<br />2.4 A 12
<br />288
<br />20
<br />1
<br />9
<br />10
<br />20
<br />1
<br />1800
<br />BAKERY OVEN
<br />15 A 120 BA
<br />HOT FOOD WELL
<br />18.3 A 240 U
<br />2199
<br />30
<br />2
<br />11
<br />12
<br />20
<br />2
<br />816
<br />BAKERY OVEN
<br />6.8 A 24010 BA
<br />400l3P
<br />- I
<br />8. DO NOT INSTALL ANY OUTLETS BACK TO BACK IN STUD WALLS.
<br />9. UNLESS OTHERWISE NOTED, WHERE TWO SWITCHES CONTROL THE LIGHTING
<br />FIXTURES IN A ROOM, CONNECT BALLASTS AND FIXTURES SO THAT ONE SWITCH
<br />CONTROLS THE OUTSIDE LAMPS AND THE OTHER SWITCH CONTROLS THE CENTER
<br />LAMP(S).
<br />2199
<br />13
<br />14
<br />816
<br />WALK-IN FAN COIL
<br />288
<br />20 1
<br />15
<br />16
<br />20 1
<br />1800
<br />151 MIXER
<br />10 BB
<br />GAS SOLENOID
<br />180
<br />20 1
<br />17
<br />18
<br />40
<br />2800
<br />WAL 240,30 L. COMF.
<br />35
<br />f 16.6
<br />10. DRAWINGS INDICATE THE LOCATION OF DEVICES, FIXTURES AND EQUIPMENT AND
<br />EXHAUST FAN #1
<br />528
<br />19
<br />20
<br />2800
<br />THE CIRCUIT NUMBER AND PANEL DESIGNATION WHICH SUPPLIES THEM. ELECTRICAL
<br />AMPS, 240V
<br />528
<br />tV3
<br />21
<br />22
<br />3
<br />2800
<br />CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CONNECTING ALL
<br />528
<br />23
<br />24
<br />40
<br />3
<br />2800
<br />WAL35 K-INCOOL. COMF.
<br />30
<br />~ O
<br />Z) Z
<br />GROUND PER N.E.C. p
<br />ART.250 Z = p
<br />O Z
<br />LIFER GROUND, 20-L OF #4 U (1) 2" EMT CONDUIT
<br />BARE CU IN BOTTOM N CONC. ~ O
<br />U 4 3/O THWN CU.
<br />FOOTING, ENCASED IN 3" OF p w o N ()
<br />CONC. z 'v & 1#6 CU. GND.
<br />v
<br />O
<br />O PNL PNL
<br />A B
<br />3/4" C, 1-#2 CU BOND TO MAIN GAS &
<br />METALLIC COLD WATER PIPE WITHIN
<br />BUILDING PER ART 250-66
<br />ELECTRICAL DEVICES TO CIRCUITS INDICATED ON THE DRAWINGS.
<br />11. USE 3M FIRE BARRIER CP 25 CAULK AT STEEL PIPE PENETRATION TRU RATED
<br />WALLS, OR EQUAL PRODUCT.
<br />12. PROVIDE MIN. OF 24" HORIZONTAL SEPARATION, IN BETWEEN ELECTRICAL BOXES
<br />LOCATED ON OPPOSITE SIDE OF WALLS PER CBC SEC. 714.3.2
<br />13. PENETRATION ON EITHER SIDE OF RATED CORRIDOR WALLS SHALL NOT
<br />EXCEED 18" S. IN. PER PENETRATION.
<br />14. ALL EXTERIOR LIGHTS SHALL HAVE PHOTO CELL CONTROL.
<br />15. TSTAT SHALL BE MOUNTED 40" TO 48" A.F.F.
<br />16. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE
<br />UNDERWRITTERS' LABORATORIES, INC. SHALL MEET THEIR REQUIREMENTS AND
<br />SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED
<br />LABEL MSERVICE IS REGULARLY FURNISHED BY THAT AGENCY.
<br />MUA
<br />852
<br />20
<br />3
<br />25
<br />26
<br />2800
<br />11.9 AMPS, 240V
<br />952
<br />27
<br />28
<br />2800
<br />952
<br />29
<br />30
<br />40
<br />3
<br />2800
<br />WALK-IN FREZ.COM
<br />35 A 240 30
<br />EXHAUST FAN #2
<br />528
<br />31
<br />32
<br />2800
<br />6.6 AMPS, 240V
<br />528
<br />AA3
<br />33
<br />34
<br />2800
<br />528
<br />35
<br />36
<br />20 1
<br />180
<br />PLUG - ROOF
<br />MERCHANDISER.COM
<br />30 A 240.30
<br />2400
<br />40
<br />37
<br />38
<br />00
<br />13,044
<br />SUB-PANEL B
<br />2400
<br />39
<br />40
<br />9600
<br />2400
<br />41
<br />42
<br />13,496
<br />17. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE
<br />WATTS: OA= 35,639 OB= 33,579 OB= 22,408
<br />SIZE NAD LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE.
<br />1/2"x8'L ROD ART 250-83,84
<br />CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS
<br />TOTAL WATTS: = 92,626 AMPS: = 381.7 A
<br />AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE
<br />RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID
<br />F.L.A. @ 125% CONT. LOAD -
<br />INTERFERENCE WITH OTHER TRADES.
<br />F.L.A. @ 125% LARGEST EQUIPMENT - 390.4 A
<br />II& ALL LUMINARIES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER
<br />1. VERIFY SHORT CIRCUIT AMPRAGE KAIC RATING WITH MID BEFORE INSTALLATION.
<br />TO THE CALIFORNIA ENERGEY COMMISSION. ALL FLUORESCENT FIXTURES TO BE
<br />2. VERIFY DISC. SWITCH FOR EQUIP. BEFORE INSTALLATION.
<br />LAMPED WITH F032, T8, 3500K LAMPS OR APPROVED EQUAL, AND HAVE AN
<br />ENERGY SAVING W SOUND RATING ELECTRONIC BALLAST OR APPROVED EQUAL
<br />UNLESS OTHERWISE SHOWN. ALL H.I.D. LIGHT FIXTURES SHALL HAVE HIGH
<br />POWER FACTOR BALLASTS.
<br />19. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF.
<br />20. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE
<br />INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY
<br />MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT
<br />MOUNTING: SURFACE PANEL: g- NEW MAIN: 200 q
<br />120/240 VOLT 30 PHASE 4 WIRE BUS: 200 q
<br />LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES,
<br />ROADWAYS, WALKS, CURBS, WALLS, EXISTING UNDERGROUND INSTALLATIONS
<br />TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER.
<br />21. CONNECT T-BAR DROP-IN FIXTURES AT DIAGNOAL CORNERS DIRECTLY TO STRUCTURE
<br />OVERHEAD USING MINIMUM #12 WIRE. CLIPS ARE NOT SUITABLE IN SEISMIC ZONE #4.
<br />LOCATION
<br />WATTAGEWATTAGE
<br />2
<br />(7
<br />J
<br />U
<br />W
<br />U
<br />Y
<br />00
<br />U
<br />U
<br />U
<br />U
<br />or
<br />Y0
<br />m
<br />U
<br />2
<br />U
<br />W
<br />=
<br />C9
<br />LOCATION
<br />22. SEPARATE PERMIT REQUIRED FOR SIGNS.
<br />23. ALL EQUIPMENT SHALL BE HARD WIRED UNLESS SUPPLIED WITH AN APPROVED FACTORY
<br />INSTALLED CORD AND MALE CORD END.
<br />OA
<br />OB
<br />OC
<br />OA
<br />OB
<br />0C
<br />(E) OVER HEAD SECONDARY (E) BUILDING ELECTRICAL SERVICE PANEL
<br />600AMP/120V/240V/30, 4W BUS BARS -
<br />- -
<br />M M 1
<br />(E) TYP. METER M
<br />PROVIDE MINIMUM LIG14TING AS FOLLOWS:
<br />1- WALK-IN REFRIGERATION UNIT ( 10 FOOT CANDLES AT 30 INCHES ABOVE THE FLOOR)
<br />2- DRY FOOD STORAGE AREA ( 10 FOOT CANDLES AT 30 INCHES ABOVE THE FLOOR)
<br />3- SELF SERVICE FOOD (20 FOOT CANDLES MINIMUM)
<br />4- PRODUCE OR PREPACKED FOOD (20 FOOT CANDLES MINIMUM)
<br />5- INSIDE OF REACHING-IN OR UNDER-COUNTER REFRIGERATORS (20 FOOT CANDLES MINIMUM)
<br />6- HAND WASHING, WARE WASHING AND EQUIPMENT AND UTENSIL STORAGE AND TOILET ROOMS
<br />(20 FOOT CANDLES MINIMUM AT 30 INCHES ABOVE THE FLOOR)
<br />7- FOOD EMPLOYEE IS WORKING WITH FOOD OR WORKING WITH UTENSILS OR EQUIPMENT SUCH
<br />AS KNIVES, SLICERS, GRINDERS, OR SAWS WHERE EMPLOYEE SAFETY IS A FACTOR
<br />MEAT GRINDER
<br />8.9 A 240 10
<br />1068
<br />20
<br />2
<br />1
<br />2
<br />20
<br />1
<br />612
<br />LIGHTS
<br />1068
<br />3
<br />4
<br />20 1
<br />240
<br />LIGHTS
<br />MEAT GRINDER
<br />8.9 A 240 10
<br />1068
<br />20
<br />2
<br />5
<br />6
<br />20
<br />1
<br />80
<br />LIGHTS
<br />1068
<br />7
<br />8
<br />MEAT GRINDER
<br />8.9 A 240 10
<br />1068
<br />20
<br />9
<br />10
<br />10682
<br />11
<br />12
<br />13
<br />14
<br />(50 FOOD CANDLES MINIMUM)
<br />15
<br />16
<br />17
<br />18
<br />c600/3PI (
<br />C200/1 P c 200/3P c 200/3P 200/1 P b 100/1 P
<br />RACE WAY EXPOSED OR CONCEALED
<br />19
<br />20
<br />- - _
<br />RACE WAY INSTALLED BELOW FLOOR -PVC
<br />2 PROVIDE 3" CONCRETE ALL AROUND RACEWAY
<br />21
<br />22
<br />23
<br />24
<br />(E) (E) (E) (E) (E)
<br />. O LIGHT FIXTURE: CONNECT TO BRANCH CIRCUIT SHOWN (e.g. CIRCUIT 2)
<br />25
<br />26
<br />40
<br />2400
<br />MERCHANDISER.COM
<br />30 A 240,30
<br />PNL PNL PNL PNL PNL
<br />L- (A) (B) (C) (A) (A)
<br />SUITE 441 SUITE 441 SUITE 441 SUITE 447 FL SECOND
<br />ROOF AC FLOOR
<br />RESIDENCE
<br />27
<br />28
<br />3
<br />2400
<br />a
<br />AO SWITCHING
<br />WALL LIGHT SWITCH, SINGLE POLE; (N) BOX CENTERLINE MOUNTING HEIGHT 45" A.F.F.
<br />29
<br />30
<br />2400
<br />31
<br />32
<br />40
<br />2400
<br />MERCHANDISER,240.3.COM
<br />30 A 240 30
<br />33
<br />34
<br />2400
<br />GROUND PER N.E.C.
<br />ART.250
<br />3
<br />OS
<br />WALL OCCUPANCY SENSOR: BOX CENTERLINE MOUNTING HEIGHT 45" A.F.F.
<br />D
<br />DIMMER CONTROL: LEVITON IP710-DLX, WHITE, SINGLE POLE, BOX CENTERLINE
<br />35
<br />36
<br />2400
<br />MERCHANDISER.COM
<br />30 A. 24030 V
<br />.2400
<br />40
<br />2400
<br />MERCHANDISER. COMF.
<br />30 A 240.30
<br />2400
<br />LL11
<br />2400
<br />MOUNTING HEIGHT 45" A.F.F.
<br />(E) LIFER GROUND, 20'L OF 3/0
<br />PER CEC 250.50(C)
<br />33
<br />{�T
<br />b TWIST TIMER; 15 MINUTE, NO HOLD, INTERMATIC FF15MC; BOX MOUNTING HEIGHT 45" A.F.F.
<br />62 RECEPTACLE OUTLET; DUPLEX; NEMA CONFIGURATION AND RATING 5-20 (2 POLE, 3 WIRE,
<br />2400
<br />+_v
<br />2400
<br />WATTS: OA= 13,496 OB= 13,044 OO1B= 9,600
<br />20A, 120V) OUTLET BOX CENTERLINE MOUNTING HEIGHT 18" A.F.F.; CONNECT TO BRANCH
<br />TOTAL WATTS: = 36,140 AMPS: =150.6 A1,
<br />(E) BOND TO MAIN GAS &+48
<br />METALLIC COLD WATER PIPE WITHIN
<br />BUILDING PER ART 250-104(B)
<br />CIRCUIT SHOWN (e.g. CIRCUIT 2)
<br />SAME; EXCEPT HEIGHT A.F.F. SHOWN
<br />d GFCISAME; EXCEPT CLASS A GFCI
<br />F.L.A. @ 125% CONT. LOAD-31.6
<br />F.L.A. @ 125% LARGEST EQUIPMENT - 158.1
<br />(E) 1/2"x8'L ROD -
<br />6 WP SAME, EXCEPT WATER PROOF
<br />QUADRUPLEX RECEPTACLE OUTLET (TWO DUPLEX)
<br />CEILING MOUNTED SHOW WINDOW RECEPTACLE OUTLETS
<br />® FLOOR MOUNTED RECEPTACLE OUTLET; DUPLEX;
<br />I ❑ DISCONNECT SWITCH
<br />JD JUNCTION BOX
<br />TELEPHONE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET
<br />EXCEPT WHERE SHOWN
<br />DATA / TELEPHONE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET
<br />EXCEPT WHERE SHOWN
<br />N DATA / TV CABLE OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET EXCE
<br />WHERE SHOWN
<br />-> DUAL HDMI OUTLET; MOUNTING HEIGHT SAME AS ADJACENT 120V RECEPTACLE OUTLET EXCEPT
<br />WHERE SHOWN
<br />EXISTING ELECTRICAL SERVICE
<br />SINGLE LINE DIAGRAM
<br />2 3 0 1 Coffee Road #B ♦ Modesto, CA 95355
<br />Phone: 209 - 408-0674 # edmond@etjarchitect.com
<br />ARCHITECT:
<br />THE DRAWINGS, SPECIFICATIONS, DESIGN AND IDEAS
<br />DESCRIBED HEREIN SHALL REMAIN THE PROPERTY OF
<br />THE ARCHITECT AND NO PART THEREOF CAN BE COPIED,
<br />DUPLICATED, DISCLOSED TO OTHERS OR USED IN
<br />CONNECTION WITH ANY WORK OR PROJECT OTHER THAN
<br />THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN
<br />PREPARED AND DEVELOPED WITHOUT EXPRESS WRITTEN
<br />PERMISSION OF THE ARCHITECT.
<br />EDMOND T. JACOBS ARCHITECT COPYRIGHT 2022
<br />CONSULTANT
<br />PROJECTADDRESS:
<br />MANTECA FOOD
<br />TENANT IMPROVEMENT
<br />KITCHEN
<br />& MEAT AREA
<br />REMODEL
<br />441 N. MAIN ST.
<br />MANTECA, CA 95336
<br />CLIENT:
<br />MR. EMAD MOHSEN
<br />447 N. MAIN STREET
<br />MANTECA, CA 95336
<br />DATE:
<br />MARCH 11, 2022
<br />DRAWN:
<br />ETJ
<br />FILE:
<br />331-21E1
<br />PROJECT NO: 329-21
<br />PERMIT NO:
<br />DESCRIPTION:
<br />NOTES / SINGLE
<br />LINE DIAGRAM
<br />SCHEDULE
<br />SHEET NO.
<br />F
<br />E-1