Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by 0 Manufacturer 0 Industry Standard El Professional Engineer <br /> Test Type © Pressure El Vacuum E Hydrostatic <br /> Test Equipment Used: OMNTEC Proteus CLD Series <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Bravo Bravo Bravo <br /> Sump Depth (inches) 79 79 79 <br /> Sump Bottom to Top of 9 9 9 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:28 11:28 10:35 <br /> Initial Reading 8.017 10.607 3.817 <br /> Test End Time 11:43 11:43 11:08 <br /> Final Reading 8.017 10.607 3.817 <br /> Change in Reading 0.0000 0.0000 0.0000 <br /> Pass Fail Criteria 0.0020 0.0020 0.0020 <br /> Tightness Test Results F1 Pass rl Fail F1 Pass r] Fail 0✓ Pass 0 Fail [Cl Pass © Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 UDC 5-6 UDC 7-8 <br /> Sump Manufacturer OPW OPW OPW OPW <br /> Sump Depth (inches) 30 30 30 30 <br /> Sump Bottom to Top of 12 12 12 12 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time x 13:02 13:02 13:17 <br /> Initial Reading x 12.269 9.122 10.496 <br /> Test End Time x 13:17 13:17 13:32 <br /> Final Reading x 12.269 9.122 10.496 <br /> Change in Reading x 0.0020 0.0000 0.0000 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results © Pass © Fail 0 Pass 0 Fail Pass Fail I Pass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />