Laserfiche WebLink
Aboveground Petroleum Storage Act Program Inspection Report <br />Date: <br />August 19, 2025 <br />Facility Address: <br />3807 Coronado AVE, StocktonSprint United Managemnt Co. <br />Facility Name: <br />Environmental Health Department <br />69 Code of Fed Regulations 112.8(d)(4) 4030026 - Aboveground valves, piping, and appurtenances are regularly <br />inspected <br />OBSERVATION: The facility failed to regularly inspect aboveground valves, piping, and appurtenances. The monthly <br />Visual Inspection Log included in Appendix B of the SPCC Plan addresses inspection of all valves, piping, and <br />appurtenances. Records of monthly inspections past October 2023 were not available at the time of inspection and Data <br />Center Operations Manager Juan Aguilera stated that monthly inspections have not been conducted. <br />REGULATION GUIDANCE: (d)(4) Regularly inspect all aboveground valves, piping, and appurtenances. During the <br />inspection, you must assess the general condition of items, such as flange joints, expansion joints, valve glands and <br />bodies, catch pans, pipeline supports, locking of valves, and metal surfaces.] <br />CORRECTIVE ACTION: Immediately inspect all required components, including but not limited to valves, piping, and <br />appurtenances and ensure inspections are done regularly. Provide proof of correction to the EHD. <br />This is a (Class 2) Violation. <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD <br />Page 8 of 9EHD - CUPA Inspection Report IS02 8/25/2025FA0003819 PR0527630 4539855