Laserfiche WebLink
motor shall be separated by a full terminal board. Epoxies or other <br /> secondary sealing systems are not considered acceptable. <br /> G. Check Valves <br /> See Section 15200.2.10 — Ball Check Valves for requirements. _ <br /> H. Gate Valves <br /> See section 15200.2.11 — Plug Valves for requirements. <br /> I. Accessories <br /> Pump stations shall be provided with the following accessories, installed as shown on <br /> the plans or as recommended by the pump manufacturer: <br /> 1. Access hatches <br /> 2. Two 2 inch guide rails per pump. <br /> 3. Upper guide bar brackets. <br /> 4. Intermediate guide bar brackets. <br /> 5. Safety cable hooks. <br /> 6. Cable holders <br /> 7. Cable support grips. <br /> 8. Anchor bolts, Type 316 stainless steel. — <br /> 9. Stainless steel lifting chain. <br /> J. Access Hatches <br /> Access hatches for the wet well and valve vault shall have clear openings as indicated <br /> on the Drawings. -- <br /> Door leaf shall be 1/4" aluminum diamond pattern plate fabricated to withstand 300 psf <br /> loading. Channel frame shall be 1/4" structural grade aluminum. <br /> Door shall be equipped with heavy duty stainless steel hinges, stainless steel pins, <br /> compression spring operators for easy operation, and an automatic hold open arm with <br /> release handle. A snap lock with removable handle shall be provided. Mill finish with — <br /> bituminous coating applied to exterior of the frame prior to embedment. Manufacturer <br /> shall guarantee proper operation and against defects in material and workmanship for a <br /> period of five years. The door shall be equipped with a covered, recessed padlock <br /> mechanism. <br /> Wetwell access hatches shall include "Safe Hatch" fall protection fiberglass grating, or <br /> equal. The fall protection grating shall be designed to combine covering of the access <br /> opening per OSHA Standard 1910.23 and shall include fall through protection and <br /> controlled confined space entry. _ <br /> Division III-127 NEI Phase II Water and Sewer — <br /> July 2007 CIP Nos. 7468,7589,7590 <br />