20-2.25 BACKFLOW PREVENTERS <br /> • Backflow preventers shall be one of the reduced pressure principle devices as specified in these specifications and <br /> the special provisions. <br /> • Backflow preventers shall be factory assembled and shall include 2 check valves, one pressure differential relief <br /> valve,2 shut-off valves and 4 test cocks. Backflow preventer and valves shall be the same size as the pipeline in which they <br /> are installed,unless otherwise shown on the plans. <br /> • Backflow preventer shut-off valves shall be manufactured from iron or bronze and shall be either resilient wedged <br /> gate valves, resilient seated and fully ported ball valves, or resilient seated butterfly valves. Threaded type shut-off valves <br /> shall be provided with a union on one side of each valve. Unions shall be brass or malleable iron. <br /> Section 20-5.03J, "Check and Test Backflow Preventers,"of the Standard Specifications is amended to read: <br /> 20-5.03J Check and Test Backflow Preventers <br /> • Backflow preventers shall be checked and tested for proper operation by a certified Backflow Preventer Tester. The <br /> tester shall hold a valid certification as a Backflow Preventer Tester from the local governing authority in which the device to <br /> be tested is located. The local governing authority shall be the county,city or water purveyor having the governing authority <br /> over testing of backflow preventers involved. If the local governing authority does not have a certification program for <br /> Backflow Preventer Testers,the tester shall have a certificate from one of the following: <br /> A. The American Water Works Association. <br /> B. A county which has a certification program for Backflow Preventer Testers. <br /> • Tests for proper operation shall conform to the requirements of the governing authority. <br /> • The Engineer shall be notified at least 5 days prior to testing backflow preventers. <br /> • One copy of the test results for each backflow preventer tested shall be furnished to the Engineer. <br /> • Backflow preventers,installed by the Contractor,failing required tests shall be repaired at the Contractor's expense. <br /> SECTION 27: CEMENT TREATED BASES <br /> Issue Date: January 5,2007 <br /> The first paragraph of Section 27-1.02, "Materials,"of the Standard Specifications is amended to read: <br /> • Cement shall be Type II portland cement conforming to the provisions in Section 90-2.01A, "Cement." <br /> The third paragraph of Section 27-1.02, "Materials,"of the Standard Specifications is amended to read: <br /> • Aggregate for use in Class A cement treated base shall be of such quality that when mixed with cement in an amount <br /> not to exceed 5 percent by mass of the dry aggregate and compacted at optimum moisture content, the compressive strength <br /> of a sample of the compacted mixture shall not be less than 5.2 MPa at 7 days,when tested by California Test 312. <br /> The fourth paragraph of Section 27-1.02, "Materials,"of the Standard Specifications is amended to read: <br /> • Aggregate for use in Class B cement treated base shall have a Resistance(R-value)of not less than 60 before mixing <br /> with cement and a Resistance(R-value)of not less than 80 after mixing with cement in an amount not to exceed 2.5 percent <br /> by mass of the dry aggregate. <br /> SECTION 28: LEAN CONCRETE BASE <br /> Issue Date: January 5,2007 <br /> The first paragraph of Section 28-1.02, "Materials,"of the Standard Specifications is amended to read: <br /> • Cement shall be Type II portland cement conforming to the provisions in Section 90-2.O1A, "Cement." <br /> The sixth paragraph of Section 28-1.02, "Materials," of the Standard Specifications is amended to read: <br /> Contract No. 10-0M7104 <br /> 19 <br />