Laserfiche WebLink
SECONDARY LINE TESTING <br />_ ................... <br />_............................. <br />Test Method By Manufacturer • Industry Standard 0 Professional Engr. 0 Other (see below) <br />Test Method Uses: • Pressure vacuum HydrostaticO Other (see below) <br />:.:..... <br />Measuring Equipment Used: Pressure Gauge (range 0 to 10 sig) ; <br />Description <br />Piping Run #1 <br />Pipe Manufacturer <br />Ameron <br />Pipe Type <br />FRP <br />Primary Pipe Diameter (inches) <br />Z. <br />Secondary Pipe Diameter (inches) <br />3" <br />Product Stored <br />Diesel <br />Method of secondary pipe isolation <br />N/A <br />Location of secondary pipe isolation <br />N/A <br />Estimated length of piping run (feet) <br />5 <br />(include length of branch runs) <br />Wait time for pressure to stabilize (hr:min) <br />Not Testable <br />Test start time <br />Initial pressure (psig) <br />Test end time <br />Final pressure (psig) <br />Test duration (hours:minutes) <br />Change in pressure (psig) <br />Pass/Fail threshold (psig) <br />TEST RESULT FAIL <br />Comments: <br />This secondary line is not testable. There is no way to isolate the line from the sump the way <br />the system is constructed. The braided flex connector extends into the secondary line and the <br />secondary line does not extend into the sump. <br />2002 Walton Engineering, Inc. <br />