SWRCA, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page C of <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />'rest Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Specify) <br />_ <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />UDC # 9&10 UDC # UDC # UDC # <br />UDC Manufacturer: <br />Unknown <br />UDC Material: <br />Fiberglass <br />UDC Depth: <br />32" <br />_ <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />11" <br />_ <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />5" <br />Condition of UDC prior to <br />testin : <br />Dry <br />_ <br />Portion of UDC Tested <br />Water Line 13" <br />_ <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />X Yes No ❑ NA <br />_ <br />Turbine shutdown response time <br />Not Alarmed <br />Is system programmed for fail- <br />safe shutdown?" <br />X Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />operational?* <br />❑ Yes X No ❑ NA <br />Wait time between applying <br />water and starting test <br />10 Minutes <br />Test Start Time: <br />10:50 <br />Initial Reading (Ri): <br />.001 <br />Test End Time: <br />11:20 <br />Final Reading (RF): <br />.001 <br />_ <br />Test Duration: <br />30 Minutes <br />_ <br />Change in Reading (RF-Ri): <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />Test Result: <br />X Pass ❑ Fail <br />Pass ❑ Fail <br />Pass ❑ Fail <br />Pass ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />Yes ElNo ❑ NA <br />Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after ter ? <br />X Yes 11No ❑ NA <br />Yes 11No 11NA <br />Yes ❑ No F-1NAYes <br />❑ No El NA <br />Comments — (include information on repairs made prior to testing, and recommended follok,-rip for failed tests) <br />All Penetrations enter from Bottom of Bravo System UDUS. <br />i If the entire depth of the UDC is not tested, specify how much was tested. If the answer to Any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />