RECEIVE <br /> SEP 2 8 2016 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br /> 18. UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑vacuum N Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: INCON TS-STS Equipment Resolution:0.0001 <br /> UDC# 1-2 UDC#3A UDC#5-6 UDC#7-8 <br /> UDC Manufacturer: WAYNE WAYNE WAYNE WAYNE <br /> UDC Material: PLASTIC PLASTIC PLASTIC PLASTIC <br /> UDC Depth. 33" 33" 29" 30" <br /> Height from UDC Bottom to Top 7" 7" 8" 9" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 6" 6" 4" 5" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to FAIR FAIR FAIR FAIR <br /> testing: <br /> Portion of UDC Tested' 12" 12" 13" 14" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ®Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA <br /> product and water)?' <br /> Turbine shutdown response time 6 SEC 6 SEC 6 SEC 6 SEC <br /> Is system programmed for fail- N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA <br /> safe shutdown? <br /> Was fail-safe verified to be N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN 15 MIN 15 MIN 15 MIN <br /> starting test <br /> Test Start Time: 12:07 12:07 12:07 12:07 <br /> Initial Reading(Rj): 13862 31782 27422 61560 <br /> Test End Time: 12:22 12:22 12:22 12:22 <br /> Final Reading(RF): 13853 31777 27419 61558 <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Chane in Reading(RF-R): 0.0009 0.0005 0.0003 0.0002 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> .Test Result: - Pass Fair 'Pass Fail:' :Pass Fail Pass Fail <br /> Was sensor removed for testing? Yes No NA Yes No NA Yes No NA Yes No NA <br /> Was sensor properly replaced and N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA N Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended fallow-up for failed rests) <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(•)is"NO"or"NA",the entire UDC must be tested. (See S WRCB LG-160) <br /> Secondary Containment Test Results 10 of 15 <br />