Laserfiche WebLink
RECEIVED <br /> SFP292016 <br /> 19. UNDER-DISPENSER CONTAINMENT DC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard Profes <br /> ❑Other(Spec) NVIRTML HEALTH <br /> Test Method Used: ❑Pressure ❑Vacuum Z Hydro. <br /> RWARTMRAT <br /> ❑Other(Sped) <br /> Test Equipment Used:INCON TS-STS Equipment Resolution:0.0001 <br /> UDC#5-6 UDC#11 SAT UDC#11-12 UDC#12-13 SAT <br /> UDC Manufacturer: WAYNE WAYNE WAYNE WAYNE <br /> UDC Material: PLASTIC PLASTIC PLASTIC PLASTIC <br /> UDC Depth: 33" 29„ 30" <br /> Height from UDC Bottom to Top 7" 8" 9" 8" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 6" 4" 5" 4" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to FAIR FAIR FAIR FAIR <br /> testing: <br /> Portion of UDC Tested' 12" 13" 14" 13" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA <br /> product and water)?* <br /> Turbine shutdown response time 6 SEC 6 SEC 6 SEC 6 SEC <br /> Is system programmed for fail- Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA <br /> safe shutdown?' <br /> Was fail-safe verified to be ®Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN 15 MIN 15 MIN 15 MIN <br /> starting test <br /> Test Start Time: 1:36 1:36 1:36 1:36 <br /> Initial Reading 43133 37864 50303 37508 <br /> Test End Time: 1:51 1:51 1.51 1:51 <br /> Final Reading(RF): 43125 37865 50276 37510 <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Change in Reading Rr): 0.0008 0.0001 0.0027 0.0002 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> 'Test Result Pass Fail" .Puss Fail' .Pass Fait Fria Fail <br /> Was sensor removed for testing? L9 Yes Lj No Lj NA MyesONOLJNA Yes No NA Yes No NA <br /> Was sensor properly replaced and Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA Z Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(include i*ormaiion on repairs made prior to testing, and recommendedfollow-upfcr failed tests) <br /> 8/24/16—TROUBLESHOOTING 11/12; ELITE IV ON SITE. TIGHTENED ALL THE BOOT <br /> CLAMPS.BZ FILLED UDC ABOVE ELECRICAL ONLY-FAILED. DISP NEEDS TO BE <br /> PULLED TO MAKE REPAIRS. <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(•)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LO-160) <br /> Secondary Containment Test Results 1 I of 15 <br />