Laserfiche WebLink
RECEIVE® <br /> 20. UNDER-DISPENSER CONTAINMENT C TESTING SEP 2 8 2016 <br /> Test Method Developed By: ❑UDC Manufacturer ® Industry Standard ❑Professional Engineer <br /> Other(S ENVIRONMENTAL HEA LTH <br /> Test Method Used: ❑Pressure ❑vacuum ®HydrosPARTM ENT <br /> ❑Other(Spec) <br /> Test Equipment Used:INCON TS-STS Equipment Resolution:0.0001 <br /> UDC#10 SAT UDC#15-16 UDC# UDC# <br /> UDC Manufacturer: WAYNE WAYNE <br /> UDC Material: PLASTIC PLASTIC <br /> UDC Depth: 29" 33" <br /> Height from UDC Bottom to Top 8„ 7„ <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 4" 61, <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to FAIR FAIR <br /> testing: <br /> Portion of UDC Tested' 13" 12" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> product and water)?' <br /> Turbine shutdown res nse time 6 SEC 6 SEC <br /> Is system programmed for fail- <br /> 9. ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> safe shutdown. <br /> Was fail-safe verified to be ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> operational?' <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN 15 MIN <br /> starting test <br /> Test Start Time: 1:28 1:28 <br /> Initial Reading(R,): 21358 12992 <br /> Test End Time: 1:43 1:43 <br /> Final Reading(RF): 21359 12999 <br /> Test Duration: 15 MIN 15 MIN <br /> Change in Reading(RF-111): 0.0001 0.0007 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 <br /> aTestl7t9ult: Pass e Fail .:.- Pass' Fail Pass Fail- Pass -Fail. <br /> Was sensor 0 Yes El No ED NA I N Yes Lj No LJJ NA Yes No NA Yes No NA <br /> Was sensor properly replaced and ®yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br /> Secondary Containment Test Results 13 of 15 <br />