Laserfiche WebLink
RECEIv tv <br /> SEP 2 9 2016 <br /> 9. TANK ANNULAR TESTING q�a1 <br /> Test Method Developed By: E] ElTank Manufacturer ®Industry Standard ENVIRUN �L HEAD H <br /> E] Other(Spec) ARTMENI <br /> Test Method Used: ❑Pressure ®Vacuum ❑ Hydrost is <br /> ❑Other(Spec) <br /> Test Equipment Used:VACUUM GAUGE Equipment Resolution: 0.5" <br /> Tank#DSL 2 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑ Yes ® No ❑Yes ❑No ❑ Yes ❑ No ❑ Yes ❑No <br /> Tank Capacity: <br /> Tank Material: FG <br /> Tank Manufacturer: UNKNOWN <br /> Product Stored: DSL <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN <br /> starting test: <br /> Test Start Time: 11:30 <br /> Initial Reading(Rj): -10" " <br /> Test End Time: 12:30 <br /> Final Reading(RF): -10" " <br /> Test Duration: 1 HR 1 HR 1 HR IHR <br /> Change in Reading(RF-Ri): 0 <br /> Pass/Fail Threshold or Criteria: 0 0 0 0 <br /> Test Result: ®Pass ❑ Fail ❑Pass ❑ Fail ❑Pass ❑ Fail ❑Pass ❑Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and <br /> verified functional after testin ? ®Yes[-INo❑NA ❑Yes❑No[:1NA ❑Yes E]No[:]NA El Yes❑No ElNA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 10. <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br /> Secondary Containment Test Results 4 of 15 <br />