REC <br /> SEP 2 9 2016 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br /> PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ®Industry Standard ❑ Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ® Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: INCON TS-STS Equipment Resolution:0.0001 <br /> Sump#DSL 2 Sump#DSL 2 Sump# Sump# <br /> Sump Diameter: 36" 36" <br /> Sump Depth: 59" 59" <br /> Sump Material: FG FG <br /> Height from Tank Top to Top of 27" 27" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 19" 19" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: FAIR FAIR <br /> Portion of Sump Tested' <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> product and water)?* <br /> Turbine shutdown response time 6 SEC 6 SEC <br /> Is system programmed for fail-safe <br /> ®Yes❑No❑NA [DYes❑No E]NA ❑Yes E]No E]NA El Yes 1-1No E]NA <br /> shutdown? <br /> Was fail-safe verified to be <br /> operational?. ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15 MIN 15 MIN <br /> test: <br /> Test Start Time: 2:28 3:23 <br /> Initial Reading(Ri): 27356 45175 <br /> Test End Time: 2:43 3:39 <br /> Final Reading(RF): 27018 45163 <br /> Test Duration: 15 MIN 15 MIN <br /> Change in Reading(RF-Rj): 0.0038 0.0012 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 <br /> Test Result: ❑Pass ®Fail ®Pass ❑ Fail ❑Pass ❑Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ®Yes❑No❑NA ®Yes❑No❑NA El Yes❑No[:1 NA El Yes El No ElNA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 8/24/16—RE-TESTED DSL 2 SIPHON&PASSED. <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br /> Secondary Containment Test Results 9 of 15 <br />