My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2016 - 2018
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
C
>
CHARTER
>
1033
>
2300 - Underground Storage Tank Program
>
PR0232352
>
COMPLIANCE INFO_2016 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/26/2022 2:10:29 PM
Creation date
11/2/2018 4:33:55 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2016 - 2018
RECORD_ID
PR0232352
PE
2361
FACILITY_ID
FA0003829
FACILITY_NAME
VANCO TRUCK-AUTO PLAZA
STREET_NUMBER
1033
Direction
W
STREET_NAME
CHARTER
STREET_TYPE
WAY
City
STOCKTON
Zip
95206
APN
16323041
CURRENT_STATUS
01
SITE_LOCATION
1033 W CHARTER WAY
P_LOCATION
01
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\rtan
Supplemental fields
FilePath
\MIGRATIONS\C\CHARTER\1033\PR0232352\COMPLIANCE INFO 2016 - 2017.PDF
QuestysFileName
COMPLIANCE INFO 2016 - 2017
QuestysRecordDate
8/8/2018 11:06:32 PM
QuestysRecordID
3201703
QuestysRecordType
12
QuestysStateID
1
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
330
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑ Other(Spec) <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: INCON TS-STS Equipment Resolution:0.0001 <br /> UDC#13-14 UDC# 14 SAT UDC#8-9 SAT UDC#9-10 <br /> UDC Manufacturer: WAYNE WAYNE WAYNE WAYNE <br /> UDC Material: PLASTIC PLASTIC PLASTIC PLASTIC <br /> UDC Depth: 30" 29" 29" 30" <br /> Height from UDC Bottom to Top 91, 8" 8" 9" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 5" 4" 4" 5" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to FAIR FAIR FAIR FAIR <br /> best" <br /> Portion of UDC Tested' 14" 13" 13" 14" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ®Yes❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA <br /> product and water)?' <br /> Turbine shutdown response time 6 SEC 6 SEC 6 SEC 6 SEC <br /> Is system programmed for fail- <br /> safe shutdown?' ®Yes❑No❑NA ®Yes[-INo[_1NA ®Yes[-INo ElNA ®Yes[:1No[-INA <br /> Was fail-safe verified to be <br /> operational?' ®Y ❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA ®Yes❑No❑NA <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN 15 MIN 15 MIN 15MIN <br /> starting test <br /> Test Start Time: 11:31 11:31 1:28 1:28 <br /> Initial Reading(Rj): 42466 31653 34364 41686 <br /> Test End Time: 11:46 11:46 1:43 1:43 <br /> Final Reading(RF): 42465 31621 34341 38950 <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Chane in Reading(RF-Ri): 0.0001 0.0032 0.0021 0.2736 <br /> Pass/Fa'l Threshold or Criteria: 0.002 0.002 0.002 <br /> Test;Result: Pass Fail Pass Fail El Pass Fail Pass Fail <br /> Was sensor removed for testing? ®Yes Lj No❑NA Z Yes❑No❑NA Ej Yes❑No❑NA Yes❑No NA <br /> Was sensor properly replaced and <br /> verified functional after testing? ®Yes[_1 No[-INA ®Yes[__1 No E]NA El Yes[_1 No[INA ®Yes E]No E]NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> RECEIVED <br /> SEP 2 9 2016 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br /> Secondary Containment Test Results 12 of 15 <br />
The URL can be used to link to this page
Your browser does not support the video tag.