SWRCB; January 20020 <br />i Page 6 <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps M <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Surnp Manufacturer Industry Standard LJ Professional Engineer <br />El Other (Specify) <br />Test Method Used: <br />Q <br />Pressure Vacuum Hydrostatic <br />Other (Specify) <br />Test Equipment Used: vplt <br />Fi11 Sump # 1 DIE Fill Sump # 2 DIE <br />Sump Diameter: 48 " 4 8" <br />Equipment Resolution: vplt to gph <br />Fill Sump # 3 LUB Fill Sump # 4 USE <br />4811 4811 <br />Sump Depth: <br />81" <br />81" <br />81" <br />52" <br />Height from Tank Top to Top of <br />Highest Piping Pentration: <br />n/a <br />n/a <br />n/a <br />n/a <br />Height from Tank Top to <br />Lowest Electrical Pentration: <br />1211 <br />121, <br />12 " <br />181, <br />Condition of Sump prior to <br />testing: <br />good <br />good <br />good <br />good <br />Portion of Sump Tested: <br />14 " <br />1411 <br />1411 <br />2011 <br />Sump Material: <br />fibergls <br />fibergl <br />fibergl <br />fibergl <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />5min <br />5min <br />5min <br />5min <br />Test Start Time: <br />8:26 <br />B:49 <br />9:03 <br />8:45 <br />Initial Reading (14 ): <br />8.155 <br />10. 760 <br />4.495 <br />2.238 <br />Test End Time: <br />8: 56 <br />9: 19 <br />9: 3 3 <br />8: 4 7 <br />Final Reading (RF ): <br />8.131 <br />10.712 <br />4.493 <br />-14.0 00 <br />Test Duration: <br />30min <br />30min <br />30min <br />2min <br />Change inReading(RF - RI ): <br />001gph <br />.003gph <br />.000gph <br />1.3gph <br />Pass'Fall Threshold or Criteria: <br />059ph <br />.05gph <br />05gph <br />05gph <br />'rest Result. <br />P:lss <br />I� ail <br />I';is4 lx'ail <br />Pass Fail <br />Pass FE' <br />Is there a sensor in the sump? <br />Yes <br />NoYes <br />DNa <br />Lfj YesLl <br />No <br />Yes <br />No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Eyes ❑No❑NA <br />X❑ Yes L:]No[:]N <br />QYes ON4::INA <br />❑X Yes —]No ]N <br />Was sensor removed for testing? <br />x <br />yes <br />N <br />NA <br />X <br />Yes <br />DNoDNA <br />[flyes <br />N <br />NA <br />Yes [:]No❑N <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes N NA <br />Q 0 � <br />1L.�jYeS[::]NcENA <br />Yes �NcDNA <br />E Yes ❑ No�I <br />Comments - (include information on repairs made prior to testing, and recommendedfollow-up far failed tests) <br />The second set of used oil data is for trouble shooting our ores, only. <br />