PERFORMANCE <br />SPECIFICATION --- <br />SECTION VII ELECTRICAL WORK - CONTINUED <br />CO <br />PART 2 - PRODUCTS <br />2.1 IDENTIFICATION OF EQUIPMENT AND WIRING: PROVIDE IDENTIFICATION WITH <br />DYMO TAPE OR EQUAL FOR ALL SERVICE ENTRANCE AND DISTRIBUTION <br />EQUIPMENT INCLUDING MAIN SWITCHGEAR, PANELS, DISCONNECT SWITCHES, <br />CONDUITS, ETC., AND FOR MOTOR FEEDERS INCLUDING SWITCHES, STARTERS <br />AND MOTORS. <br />2.2 LIGHT FIXTURES TO BE PROVIDED BY OWNER. <br />2.3 CONDUITS: PROVIDE THE FOLLOWING TYPES OF RACEWAYS IN ACCORDANCE <br />WITH THE SPECIFIC APPLICATION OF LOCATION INDICATED. <br />2.3.1 RIGID GALVANIZED STEEL: WHERE EXPOSED TO THE WEATHER; FOR <br />ENCLOSING MAIN GROUNDING CONDUCTOR: WHERE REQUIRED FOR <br />MECHANICAL PROTECTION OR WHERE SPECIFICALLY INDICATED, MATERIAL <br />SHALL BE AS MANUFACTURED BY GERNERAL ELECTRIC, REPUBLIC <br />YOUNGSTOWN STEEL AND TUBE, OR EQUAL. PROTECT WITH ASPHALTIC <br />PROTECTIVE COATING WHEN BELOW FINISH GRADE. <br />2.3.2 SEALOFFS: WHERE CONDUITS EXIT FLOOR OR CONCRETE AT DISPENSERS, <br />AUTO GAUGING, SUBMERSIBLE PUMPS, AND INTERIOR DISTRIBUTION PANEL. <br />2.3.3PVC CONDUITS: ALL WIRING RUNS BURIED UNDERGROUND UNLESS <br />OTHERWISE INDICATED. MATERIAL SHALL BE HEAVY WALL, TYPE II RIGID <br />SCHEDULE 40 AS MANUFACTURED BY CARLON, BALDWIN, TRIANGLE, OR EQUAL. <br />PVC CONDUITS SHALL_ BE U1. LISTED AND APPROVED, <br />2.4 CONDUCTORS: <br />CON <br />SECTION VII ELECTRICAL WORK CONTINUED <br />PART 3 - EXECUTION = CONTINUED <br />G T <br />3.8 OPERATING AND ACCEPTANCE. TESTS: <br />3.8.1 CONDUCT OPERATING TEST ON ENTIRE ELECTRICAL INSTALLATION; ALL SYSTEMS <br />MUST BE COMPLETE AND IN GOOD OPERATING ORDER. REFER TO START -IJP AND FINAL <br />CHECK-OUT OF SYSTEM COVERED ELSEWHERE. <br />DO NOT START OR OPERATE EQUIPMENT WITHOUT SPECIFICDIRECTIVES OF OWNER'S <br />SPECIFIED REPRESENTATIVE. ANY DAMAGE TO OWNER'S EQUIPMENT DUE TO <br />DEFECTIVE INSTALLATION AND/OR OPERATION WILL. BE THE RESPONSIBILITY OF THAT <br />SUBCONTRACTOR FOR CORRECTION, REPLACEMENT AND/OR MONETARY COMPENSATION <br />AS REQUIRED. <br />3.8.2 MAKE INSULATION TESTS ON MAIN SERVICE EQUIPMENT AND ALL FEEDERS AND <br />PANELBOARDS. <br />3.8.3TEST GROUND: RESISTANCE TO GROUND SHALL NOT EXCEED 25 OHMS. <br />3.8.41NSPECT ALL PANELBOARDS. ALL CONNECTIONS MUST BE TIGHT AND SECURE. <br />3.9"AS-BUILT' DRAWINGS: FURNISH OWNER'S CONSTRUCTION MANAGER WITH ONE SET <br />OF MARKED -UP PRINTS SHOWING "AS -BUILT' INSTALLATION. <br />3.IOFINAL ACCEPTANACE: UPON COMPLETION OF WORK, PRESENT CERTIFICATE OF APPROVAL <br />OF LOCATION OR COVERNING INSPECTION AUTHORITY, <br />3.1 1 CLEAN-UP: CLEAN UP ALL DEBRIS CAUSED BY WORK OF THIS SECTION, KEEPING <br />THE PREMISES CLEAN AND NEAT AT ALL TIMES. - <br />SECTION VIII PAINTING <br />`tRFFS <br />SECTION IX CANOPIES - CONTINUED <br />PART 1 - GENERAL - CONTINUED <br />1.1.1 COMPLETE FABRICATION DRAWINGS INCLUDING FOOTINGS DESIGN. <br />1.1.2COMPLETE ABOVE GROUND STRUCTURAL SUPPORT SYSTEM. <br />1.1.3STEEL ROOF DECK, SMOOTH WHITE 90% REFLECTIVE PAINT. <br />1.1.4ROOF BRACING. <br />1.1.5CAP FLASHING. <br />1.1.61DOWNSPOUTS - INTERNAL INSIDE COLUMNS. <br />1.'1.7PERMITS AND INSPECTIONS. <br />1. 1.8 INSTALLATION AND FRAMING FOR OWNER -SUPPLIED FASCIA SIGNS INCLUDING ELECTRIC. <br />1. 1.9 INSTALLATION AND FRAMING FOR FASCIA MATERIAL AS PER OWNER SPECIFICATIONS. <br />PART 2 - PRODUCTS <br />2.1 ROOF STEEL DECK: ROOF STEEL DECK SHALL BE 2 1/4 " MINIMUM DEEP, 24 GAUGE <br />BAKED WHITE ENAMEL STEEL WITH MINIMUM SECTIN MODULES OF 0.25 IN 1/4 3 MOMENT <br />OF INERTIA OF 0.030 IN 14/4 4. <br />2.2 STRUCTURAL STEEL: <br />2.2.1 ALL STRUCTURAL STEEL TO BE A.S.T.M. A-36 AND SHALL COMPLY WITH THE STANDARD <br />SPECIFICATIONS FOR STRUCTURAL STEEL FOR BUILDINGS OF A.I.S.C. AND WITH THE <br />A.I.S.C. CODE OF STANDARD PRACTICE (LATEST EDITION). <br />2.2.2HIGH STRENGTH BOLTS SHALL CONFORM TO THE STANDARD SPECIFICATIN A.S.T.M. <br />A325", AND SHALL BE PROVIDED WITH CARBONIZED WASHERS UNDER THE NUTS. <br />2.2.3ALL OTHER BOLTS SHALL BE A-307 AND SHALL CONFORM TO A.S.T.M. STANDARDS, <br />*WITH WASHER REQUIRED. <br />2.2.4ALL HIGH STRENGTH BOLTS SHALL BE TORQUED TO PROVIDE A MINIMUM TENSION IN <br />BOLT OF 90% OF MINIMUM PROOF LOAD OF THE BOLT. <br />2.2.5TUBE COLUMNS SHALL COMPLY WITH A-53, GRADE B. <br />2.2.6ALI_ TUBE COLUMNS SHALL BE 46 KSI STEEL. <br />2.2.7 ALL WELDING SHALL BE WITH E70XX ELECTRODES AND BE ACCOMPLISHED BY <br />CERTIFIED WELDERS. <br />2..3 FASCIAL: <br />2.3.1 FASCIA BACKING PLYWOOD SHALL BE MINIMUM 1/2 " THICK MARINE GRADE. MARINE <br />GRADES SHALL MEET THE REQUIREMENTS OF EXTERIOR TYPE AND SHALL BE ON OF <br />GRADE 1-1, HIGH DENSITY OVERLAY. <br />2.12VERTICAL SUPPORTS SHALL. BE 14 GA STEEL. STUDS AT 14" O.C. OR 3 X 3 X 1/4 <br />STEEL ANGLES ALL AT 24" O.C. WITH CORRESPONDING MEMBERS TOP AND BOTTOM <br />SUPPORT. <br />2.3.3SCREWS FOR FASCIA SHALL BE ALUMINUM OR GALVANIZED SIZE AS REQUIRED. <br />2.3.4REFER TO PROJECT DRAWINGS FOR FASCIA MATERIAL AND INSTALLATION. MATERIAL <br />SHALL BE ONE OF THE FOLLOWING: <br />A. BACK -LIGHT FABRICATED SIGH SYSTEM <br />B. PREFIINISHED METAL FASCIA SYSTEM. <br />C. PREFINISHED FASCIA MATERIAL AS SELECTED. <br />PART 3 -- EXECUTION <br />3.1 FABRICATION DRAWINGS: <br />3. 1 .1 CANOPY CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ENGINEERED AND <br />STAMPED SHOP DRAWINGS FOR OVERHEAD STRUCTURE AND FOUNDATION SYSTEMS. <br />3.1.2DRAWINGS SHALL SHOW PROJECT LOCATION AND ADDRESS. <br />3.1.30RIGINAL ENGINEER'S STAMP FOR APPROPRIATE STATE SHALL BE AFFIXED TO <br />EACH PAGE OF DRAWINGS. <br />3.1.4SHOP DRAWINGS SHALL SPECIFICALLY CALL OUT SOILS REPORT NUMBER AND DATE <br />FOR WHICH CANOPY FOOTINGS WERE DESIGNED. <br />3.1.5SHOP DRAWINGS SHALL SPECIFICALLY CALL OUT SIZE, WEIGHT, TYPE AND NUMBER <br />OF ALL STRUCTURAL MEMBERS. <br />3.1.6ALL DESIGN LOADS SHALL COMPLY WITH U.B.0 LATEST EDITION AND LOCAL <br />BUILDING DEPARTMENT REQUIRED LOADINGS, WHICHEVER IS MOST STRINGENT. MINIMUM <br />DESIGN LOADS SHALL BE CONSIDERED TO BE: WIND 100#, LIVE 35#, UPLIFT 35# <br />AND DEAD LOAD 35# OR AS LOCAL STRUCTURAL DESIGN DICTATES, IF APPLICATION <br />IS SUBJECT TO HIGH ALTITUDE (SNOW) LOADING, DESIGN SHALL BE ADJUSTED TO <br />COMPLY ACCORDINGLY. <br />3.1.7 DEFLECTION OF ALL STRUCTURAL MEMBERS SHALL BE LIMITED TO SPAN/240 FOR <br />L. L. ONLY. <br />3.1.8 ATTACH DECK STRUCTURAL SUPPORTS WITH 3/8 " DIAMETER BOLTS. <br />3.1.9 ROOF DECK SHALL BE AN I.C.B.O. APPROVED DIAPHRAGM DECK AND ATTACHED IN <br />A MANNER THAT COULD BE CONSIDERED A DIAPHRAGM. AN ALTERNATE TO THIS IS <br />1/2" DIAMETER STEEL ROD DIAGONAL X -BRACING WITH TURNBUCKLES. LAYOUT OF <br />ROD BRACING AND CONNECTIONS TO STRUCTURAL MEMBERS SHALL BE APPROVED BY <br />STRUCTURAL ENGINEER. <br />3.1.10 CONCRETE FOOTINGS SHALL BE MADE WITH STONE AGGREGATE AND SHALL HAVE <br />A COMPRESSIVE STRENGTH TO A MINIMUM 3000 LBS. PER SQUARE INCH WITHIN 28 <br />DAYS AFTER POURING. <br />3.1.11 ALL FOUNDATION METAL REINFORCEMENT SHALL BE DEFORMED TYPE BARS <br />(EXCEPT #2 BARS) AND SHALL CONFORM TO THE REQUIREMENTS OF THE "STANDARD <br />SPECIFICATION A.S.T.M. 615 GRADE 40". <br />3.1.12 THE SHOP DRAWINGS SHALL EXPLICITLY SHOW LOCATION OF DOWNSPOUTS, <br />GASOLINE VENT LINES, ETC., AS RELATED TO ANY AND ALL UTILITIES AND/OR <br />PIPING AT COLUMN LOCATIONS. ROOF DRAINS AND LEADERS SHALL BE DIRECTED <br />DOWN THE INTERIOR CANOPY COLUMN EXITING SIDE OF ISLAND FORM, LEVEL OR ABOVE <br />FINISH GRADE OF CONCRETE SIDE PAD ON DOWNHILL SIDE OF ISLAND. DOWNSPOUTS <br />SHALL BE 4" X 4" CONSTRUCTED OF 16 GA GALVANIZED METAL OF FREEZE -PROOF <br />OR OPEN -FACE DESIGN. STRAP TO CANOPY COLUMN AT 24" O.C. <br />3.1.13 INCLUDE IN DESIGN PROVISION FOR OVERFLOW DEVICE AT OPPOSITE CORNERS OR <br />CANOPY. <br />3.1.14 CONSTRUCTION NOT SPECIFICALLY INDICATED SHALL BE ACCOMPLISHED PER <br />MINIMUM REQUIREMENTS OF THE UNIFORM BUILDING CODE, LATEST EDITION. <br />3.1.15 IF THERE ARE ANY CONFLICTS BETWEEN LINES ON DRAWINGS AND GENERAL NOTES <br />OR WITH SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS GOVERN. <br />3.1.16 ANY DEVIATION FROM THE PLANS OR SPECIFICATIONS SHALL BE APPROVED BY <br />SOUTHLAND'S CONSTRUCTION REPRESENTATIVE. <br />V) <br />z <br />0 <br />a <br />U <br />U <br />a <br />2.4.1 FURNISH AND INSTALL COLOR CODED COPPER CONDUCTORS; 600 VOLT, OF <br />SIGNAL CONTROL <br />PART 1 -- GENERAL <br />SIZES INDICATED. MINIMUM SIZE #12 (TFFN) EXCEPT FOR AND <br />m <br />CIRCUITS AND WHERE OTHERWISE NOTED, TYPE TW (60 DEGREES CENTIGRADE) <br />1.1 SCOPE:- THIS SECTION COVERS THE FURNISHING OF ALL LABOR, MATERIALS, <br />FOR GENERAL BRANCH CIRCUIT WIRING; TYEP THN (90 DEGREES CENTIGRADE) <br />SERVICES, EQUIPMENT AND APPLIANCES IN CONJUNCTION WITH OR PROPERLY INCIDENTAL <br />FOR SUPPLY CNNECTIONS TO LIGHT FIXTURES. INSTALL PER COLOR CODE OF <br />TO THE COMPLETION OF ALL PAINTING OF SURFACES COMPLETE, INCLUDING <br />NEC. <br />PAINTING OF THE FOLLOWING SURFACES: <br />2.4.2SHIELDED CABLES: PROVIDE SHIELDED CABLE FOR INTERCOM AS PER <br />1.1,1 MISCELLANEOUS METAL, DOWNSPOUNTS,; COLUMNS, POSTS, ISLAND FORMS, VENT <br />a <br />MANUFACTURER'S SPECIFICATIONS AND AS REQUIRED ON DRAWINGS. <br />LINES, MANHOLE COVERS AND ELECTRICAL CONDUITS. <br />2.5 <br />SPLICES AND CONNECTIONS: PROVIDE SPLICES ONLY IN READILY ACCESSIBLE <br />1.2 PAINTING DOES NOT INCLUDE: <br />OUTLET BOXES. PROVIDE INSULATED PRESSURE CONNECTORS OR "CRIMP -ON" <br />1.2.1 PAINTING CANOPY SOFFITS. <br />SLEEVES WITH OVERALL NYLON INSULATORS FOR CONDUCTORS. CONNECTORS <br />1.2.2 PAINTING LIGHT FIXTURES. <br />a <br />SHALL BE 3M "SCOTCHI_OK", BUCHANNAN SPLICE CAPS WITH INSULATED WRAP, <br />OR IDEAL "CRIMP -SLEEVES" WITH SCAR CAP INSULATOR OR EQUAL. <br />1.2.3 PAINTING FASCIA SIGN FRAMES. <br />2.6 <br />PANELBOARDS: <br />1.2.4 PAINTING GASOLINE EQUIPMENT. <br />z <br />2.6.1 BRANCH CIRCUIT PANELBOARDS: PROVIDE FLUSH -MOUNT CIRCUIT BREAKER TYPE <br />1.3 COLOR SCHEDULE: COLOR OF PAINTS SHALL BE AS LISTED IN COLOR ° SCHEDULE. <br />PANELBOARDS WITH THERMAL MAGNETIC, MOLDED CASE, GENERAL ELECTRIC TYPE NLRB <br />PART <br />2, - PR�DU(TS <br />OR APPROVED EQUAL, WITH PLUG-IN CIRCUIT BREAKERS, GENERAL ELECTRIC TYPE NLQF <br />2.1 PAINT MANUFACTURERS AND PRODUCTS: FAINTING SYSTEM AS SPECIFIED HEREIN IS <br />OR APPROVED EQUAL. PROVIDE GROUNDING TERMINAL BLOCK IN EACH PANELBOARD <br />BASED ON PRODUCTS OF THE GLIDDEN COATING & RESINS COMPANY, A DIVISION OF <br />SEE INDIVIDUAL PANEL SCHEDULE ON DRAWINGS, <br />SCM CORPORATION. HOWEVER, EQUAL PAINTING SYSTEMS OF PRATT & LAMBERT, PPG <br />2.6.2ACCEPTBALE SUBSTITUTES: DISTRIBUTION EQUIPMENT EQUIVALENT IN TYPE, <br />INDUSTRIES AND BENJAMIN MOORE"WILL BE CONSIDERED. <br />CLASSIFICATION AND QUALITY IN ACCORDANCE WITH NEMA STANDARDS AS MANUFACTURED <br />2.2 PAINTING COATS AND PRODUCTS: <br />BY CUTLER -HAMMER, FEDERAL_ PACIFIC, ITE, SQUARE D AND WESTINGHOUSE ARE <br />2.2.1 GASOLINE ISLAND METALS AND VENT LINES: SHALL BE GLIDDEN SPREAD LUSTRE <br />ACCEPTABLE AS SUBSITIUTIES, WHEN APPROVED IN WRITING. <br />ALKYD SEMI -GLOSS PAINT #4656 ARCHITECTURAL BROWN. <br />PART 3 - EXECUTION <br />P3,1 ART <br />2.2.2PAINT ALL MANHOLES COVERS AND 4" SURROUNDING CONCRETE, INSIDE AND OUT, <br />w <br />COORDINATE TIME SCHEDULES, INSTALLATION, HOOK-UPS AND MISCELLANEOUS <br />IN ACCORDANCE WITH STANDARD INDUSTRY COLOR CODE AS SHOWN: <br />PROCEDURES WITH ALL OTHER TRADES THAT WILL BE INVOLVED TO EXPEDITE THE <br />COMPLETION OF THE CONTRACT. THE ELECTRICAL SUBCONTRACTOR SHALL BE SOLEY <br />API COLOR CODES: <br />RESPONSIBLE FOR THE PROPER INSTALLATION OF THE ELECTRICAL WORK. <br />LEADED REGULAR SOLID BLUE <br />3.2 <br />CONDUITS: FURNISH AND INSTALL A COMPLETE OVERALL CONDUIT RACEWAY SYSTEM <br />LEADED PREMIUM SOLID RED <br />UNLEADED REGULAR WHITE W/BLACK CROSS <br />FOR ALL WIRING AND CONDUCTORS. PROVIDE SIZES AND RACEWAYS AS INDICATED ON <br />UNLEADED PREMIUM RED W/WHITE CROSS <br />DRAWINGS OR AS REQUIRED BY NATIONAL ELECTRICAL CODE FOR CONDUCTORS TO BE <br />LEADED REGULAR W/ EXTENDER BLUE W/WHITE BAND <br />CONTAINED. ALL RACEWAYS SHALL CONFORM TO THE FOLLOW REQUIREMENTS: <br />UNLEADED REGULAR W/EXTENDER WHITE W/BLACK CROSS & BLACK BAND <br />3.2.1 CONCEAL ALL CONDUIT RUNS EXCEPT WHERE EXPOSED RUNS ARE AUTHORIZED <br />UNLEADED PREMIUM W/EXTENDER RED W/WHITE CROSS & WHITE BAND <br />BY OWNER'S CONSTRUCTION MANAGER IN WRITING. <br />DIESEL SOLID .YELLOW <br />F- <br />3.2.2ACTUAL CONDUIT RUNS ARE NOT GENERALY INDICATED; CONDUITS AT TANKS <br />VAPOR RECOVERY SOLID ORANGE <br />SHALL NOT CROSS OVER TANKS. PLACE CONDUIT THROUGH EACH END OF TANK <br />PART 3 - EXECUTION <br />EXCAVATION AND PLACE FIELDS PARALLEL WITH AXIS OF TANKS. <br />3.1 PROTECTION: COVER ENTIRE CONCRETE SURFACES. NO PAINT OR SOLVENT SMALL BE <br />3 .2.3CLEAN AND DRY ALL RACEWAYS THOROUGHLY BEFORE CONDUCTORS ARE PULLED IN. <br />ALLOWED TO COME CONTACT WITH CONCRETE SURFACES. WHERE 1T BECOMES <br />3.2.4FLASH AND COUNTER FLASH CONDUITS WHICH PENETRATE THE CANOPY DECKING. <br />NECESSARY, IN ORDER TO EXECUTE .HIS OWN WORK, FOR PAINTER TO REMOVE <br />3.2.5PROVIDE SEAL -OFF FITTINGS WHERE CONDUIT RUNS ENTER OR LEAVE. <br />COVERINGS, PLATES, ETC., PLACED BY OTHER CONTRACTORS IN ANY BRANCH OF THE <br />HAZARDOUS AREAS OF DISSIMILAR CONDITIONS SUCH AS TEMPERATURE, HUMIDITY, ETC. <br />WORK, HE SHALL REPLACE SAME IN PROPER MANNER. IN SITUATIONS WHERE SAID <br />3.2.6 FURNISH AND INSTALL COMPLETE RACEWAY SYSTEM, INCLUDING CONDUITS AND <br />COVERINGS, PLATES, ETC., CANNOT BE READILY REMOVED, PAINTER SHALL PROTECT THE <br />OUTLETS, AS INDICATED AND AS REQUIRED FOR INTERCOM SYSTEM, GAS PRICE SIGNS, <br />WORK IN SOME OTHER SATISFACTORY MANNER: OILY RAGS AND WASTE MUST BE <br />SECURITY LIGHTING AND CANOPY LIGHTING SYSTEM, AND LIGHTED FASCIA SYSTEM <br />REMOVED EVERY NIGHT. UNDER NO CIRCUMSTANCES SHALL THEY BE ALLOWED TO <br />WHERE APPLICABLE, CONDUIT AMOUNTS AND SIZES SHALL BE AS SHOWN ON <br />ACCUMULATE. PAINTING SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE DONE <br />GASOLINE DRAWINGS. ADDITIONAL CONDUITS AND CIRCUITS WILL BE REQUIRED <br />TO THE WORK OF OTHER SUBCONTRACTORS AND SHALL REPAIR OR REPLACE AS <br />FOR LIGHTED FASCIA SYSTEMS. PROVIDE AS REQUIRED. <br />NECESSARY TO THE SATISFACTION OF THE, OWNER. <br />3.3 <br />LIGHTING,: INSTALL ALL LIGHTING FIXTURES AND LAMPS AS INDICATED ON DRAWINGS. <br />3.2 PREPARATION OF SURFACES: INSPECT ALL SURFACES TO BE PAINTED. REPORT ANY <br />SECURELY MOUNT ALL FIXTURES; PROVIDE ALL ADDITIONAL HANGERS AND SUPPORTS AS <br />DISCREPANCIES TO THE CONTRACTOR PRIOR TO START OF, WORK. STARTING OF PAINT <br />NECESSARY TO SECURELY FASTEN AND SUPPORT FIXTURES. CLEAN ALL FIXTURES AND <br />APPLICATION SHALL CONSTITUTE ACCEPTANCE OF SURFACES AS SUITABLE FOR THE - <br />LAMPS UPON COMPLETION OF THE PROJECT. CONTRACTOR SHALL VERIFY AMOUNT AND <br />RECEPTION OF PAINT APPLICATION. ALL SURFACES SHALL BE CLEAN AND DRY, BETWEEN <br />TYPE OF ISLAND/CANOPY LIGHTING SYSTEMS. SHOULD ADDITIONAL CONDUITS/CIRCUITS <br />50 AND 90` DEGREES FARENHEIT AT TIME OF PAINT APPLICATION, CLEAN METAL OF MILL <br />BE REQUIRED, VERIFY THROUGH LOCAL CONSTRUCTION OFFICE AND PROVIDE AS REQUIRED. <br />SCALE, RUST, OIL_; GREASE AND FOREIGN MATTER. CLEAN GALVANIZED METAL ACCORDING <br />TO SSPC-SP 1 -63 SOLVENT CLEANING. PROTECT ADJACENT AND FINISHED WORK FROM <br />3.4 <br />SIGNS AND LIGHTED FASCIAL: VERIFY FINAL LOCATIONS AND TYPE WITH OWNER. <br />PAINT. <br />FURNISH AND INSTALL ALL CONDUITS AND WIRES WITH STUB -OUTS AS DIRECTED. MAKE <br />FINAL CONNECTIONS AS REQUIRED, <br />3.3 APPLICATION OF PAINT: DO NOT THIN, -ADULTERATE OR CHANGE MATERIALS` EXCEPT <br />AS RECOMMENDED BY MANUFACTURER. EMPLOY ONLY SKILLED MECHANICS FOR WORK. ALL <br />3.5 <br />OUTLETS: COORDINATE LOCATION OF ALL ELECTRICAL EQUIPMENT, INCLUDING INTERCOM <br />PAINTING SHALL BE BRUSHED,, SPRAYED OR ROLLED EVENLY FOR THOROUGH COATS <br />OUTLETS, SWITCHES, RECEPTACLES, CONTROLLERS, PANELBOARDS, SWITCHGEAR; ETC., TO <br />WITHOUT RUNS, SACS OR OTHER BLEMISHES.' ALLOW EACH COAT TO DRY BEFORE APPLYING <br />AVOID INTERFERENCE AND OBSTRUCTIONS WITH EQUIPMENT OF OTHER CRAFTS AND TRADES <br />AV <br />AVTHAT <br />SUBSEQUENT COATS. ALL SURFACES TO RECEIVE A MINIMUM OF 2 COATS AS NECESSARY TO <br />SO ELECTRICAL EQUIPMENT WILL NOT BE BLOCKED OR MADE INACCESSIBLE OR <br />ACHIEVE AN APPROVED FINISH. APPLICATION OF PAINT, ETC.; SHALL BE IN STRICT, <br />NQPERABLE. PROVIDE WEATHERPROOF OUTLETS WHERE EXPOED TO THE WEATHER OR ' <br />COMPLIANCE WITH MANUFACFURER'S, DIRECTIONS. <br />TO MOISTURE. <br />3ACLEAN--UP. CLEAN UP ALL DEBRIS CAUSED BY THE .WORK OF THIS S 11 ECTION, KEEPING <br />3.6ISOLATED <br />GROUND: IT IS MANDATORY THAT GASOLINE EQUIPMENT REQUIRING ISOLATED <br />THE PREMISES CLEAN AND NEAT AT ALL TIMES <br />GROUND SHALL BE PROVIDED WITH SAME. MINIMUM CIRCUITS REQUIRED, BUT NOT <br />LIMITED TO, SHALL BE: INTERCOM, GAS CONSOLE AND GASOLINE TANK MONITORING SYSTEM. <br />SECTION IX CANOPIES <br />3.7 <br />EXCAVATION AND BACKFILLING: ALL EXCAVATION AND BACKFILLING NECESSARY FOR THIS <br />INSTALLATION OF ELECTRICAL WORK SHALL BE INCLUDED IN THIS SECTION AND COMPLY <br />PART 1 - GENERAL_ <br />WITH SECTION 111, EARTHWORK. <br />1,1 SCOPE: THIS SECTION COVERS THE FURNISHING AND. INSTALLATION OF ALL ITEMS FOR <br />THE INSTALLATION OF A COMPLETE GASOLINE CANOPY INCLUDING. <br />`tRFFS <br />SECTION IX CANOPIES - CONTINUED <br />PART 1 - GENERAL - CONTINUED <br />1.1.1 COMPLETE FABRICATION DRAWINGS INCLUDING FOOTINGS DESIGN. <br />1.1.2COMPLETE ABOVE GROUND STRUCTURAL SUPPORT SYSTEM. <br />1.1.3STEEL ROOF DECK, SMOOTH WHITE 90% REFLECTIVE PAINT. <br />1.1.4ROOF BRACING. <br />1.1.5CAP FLASHING. <br />1.1.61DOWNSPOUTS - INTERNAL INSIDE COLUMNS. <br />1.'1.7PERMITS AND INSPECTIONS. <br />1. 1.8 INSTALLATION AND FRAMING FOR OWNER -SUPPLIED FASCIA SIGNS INCLUDING ELECTRIC. <br />1. 1.9 INSTALLATION AND FRAMING FOR FASCIA MATERIAL AS PER OWNER SPECIFICATIONS. <br />PART 2 - PRODUCTS <br />2.1 ROOF STEEL DECK: ROOF STEEL DECK SHALL BE 2 1/4 " MINIMUM DEEP, 24 GAUGE <br />BAKED WHITE ENAMEL STEEL WITH MINIMUM SECTIN MODULES OF 0.25 IN 1/4 3 MOMENT <br />OF INERTIA OF 0.030 IN 14/4 4. <br />2.2 STRUCTURAL STEEL: <br />2.2.1 ALL STRUCTURAL STEEL TO BE A.S.T.M. A-36 AND SHALL COMPLY WITH THE STANDARD <br />SPECIFICATIONS FOR STRUCTURAL STEEL FOR BUILDINGS OF A.I.S.C. AND WITH THE <br />A.I.S.C. CODE OF STANDARD PRACTICE (LATEST EDITION). <br />2.2.2HIGH STRENGTH BOLTS SHALL CONFORM TO THE STANDARD SPECIFICATIN A.S.T.M. <br />A325", AND SHALL BE PROVIDED WITH CARBONIZED WASHERS UNDER THE NUTS. <br />2.2.3ALL OTHER BOLTS SHALL BE A-307 AND SHALL CONFORM TO A.S.T.M. STANDARDS, <br />*WITH WASHER REQUIRED. <br />2.2.4ALL HIGH STRENGTH BOLTS SHALL BE TORQUED TO PROVIDE A MINIMUM TENSION IN <br />BOLT OF 90% OF MINIMUM PROOF LOAD OF THE BOLT. <br />2.2.5TUBE COLUMNS SHALL COMPLY WITH A-53, GRADE B. <br />2.2.6ALI_ TUBE COLUMNS SHALL BE 46 KSI STEEL. <br />2.2.7 ALL WELDING SHALL BE WITH E70XX ELECTRODES AND BE ACCOMPLISHED BY <br />CERTIFIED WELDERS. <br />2..3 FASCIAL: <br />2.3.1 FASCIA BACKING PLYWOOD SHALL BE MINIMUM 1/2 " THICK MARINE GRADE. MARINE <br />GRADES SHALL MEET THE REQUIREMENTS OF EXTERIOR TYPE AND SHALL BE ON OF <br />GRADE 1-1, HIGH DENSITY OVERLAY. <br />2.12VERTICAL SUPPORTS SHALL. BE 14 GA STEEL. STUDS AT 14" O.C. OR 3 X 3 X 1/4 <br />STEEL ANGLES ALL AT 24" O.C. WITH CORRESPONDING MEMBERS TOP AND BOTTOM <br />SUPPORT. <br />2.3.3SCREWS FOR FASCIA SHALL BE ALUMINUM OR GALVANIZED SIZE AS REQUIRED. <br />2.3.4REFER TO PROJECT DRAWINGS FOR FASCIA MATERIAL AND INSTALLATION. MATERIAL <br />SHALL BE ONE OF THE FOLLOWING: <br />A. BACK -LIGHT FABRICATED SIGH SYSTEM <br />B. PREFIINISHED METAL FASCIA SYSTEM. <br />C. PREFINISHED FASCIA MATERIAL AS SELECTED. <br />PART 3 -- EXECUTION <br />3.1 FABRICATION DRAWINGS: <br />3. 1 .1 CANOPY CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ENGINEERED AND <br />STAMPED SHOP DRAWINGS FOR OVERHEAD STRUCTURE AND FOUNDATION SYSTEMS. <br />3.1.2DRAWINGS SHALL SHOW PROJECT LOCATION AND ADDRESS. <br />3.1.30RIGINAL ENGINEER'S STAMP FOR APPROPRIATE STATE SHALL BE AFFIXED TO <br />EACH PAGE OF DRAWINGS. <br />3.1.4SHOP DRAWINGS SHALL SPECIFICALLY CALL OUT SOILS REPORT NUMBER AND DATE <br />FOR WHICH CANOPY FOOTINGS WERE DESIGNED. <br />3.1.5SHOP DRAWINGS SHALL SPECIFICALLY CALL OUT SIZE, WEIGHT, TYPE AND NUMBER <br />OF ALL STRUCTURAL MEMBERS. <br />3.1.6ALL DESIGN LOADS SHALL COMPLY WITH U.B.0 LATEST EDITION AND LOCAL <br />BUILDING DEPARTMENT REQUIRED LOADINGS, WHICHEVER IS MOST STRINGENT. MINIMUM <br />DESIGN LOADS SHALL BE CONSIDERED TO BE: WIND 100#, LIVE 35#, UPLIFT 35# <br />AND DEAD LOAD 35# OR AS LOCAL STRUCTURAL DESIGN DICTATES, IF APPLICATION <br />IS SUBJECT TO HIGH ALTITUDE (SNOW) LOADING, DESIGN SHALL BE ADJUSTED TO <br />COMPLY ACCORDINGLY. <br />3.1.7 DEFLECTION OF ALL STRUCTURAL MEMBERS SHALL BE LIMITED TO SPAN/240 FOR <br />L. L. ONLY. <br />3.1.8 ATTACH DECK STRUCTURAL SUPPORTS WITH 3/8 " DIAMETER BOLTS. <br />3.1.9 ROOF DECK SHALL BE AN I.C.B.O. APPROVED DIAPHRAGM DECK AND ATTACHED IN <br />A MANNER THAT COULD BE CONSIDERED A DIAPHRAGM. AN ALTERNATE TO THIS IS <br />1/2" DIAMETER STEEL ROD DIAGONAL X -BRACING WITH TURNBUCKLES. LAYOUT OF <br />ROD BRACING AND CONNECTIONS TO STRUCTURAL MEMBERS SHALL BE APPROVED BY <br />STRUCTURAL ENGINEER. <br />3.1.10 CONCRETE FOOTINGS SHALL BE MADE WITH STONE AGGREGATE AND SHALL HAVE <br />A COMPRESSIVE STRENGTH TO A MINIMUM 3000 LBS. PER SQUARE INCH WITHIN 28 <br />DAYS AFTER POURING. <br />3.1.11 ALL FOUNDATION METAL REINFORCEMENT SHALL BE DEFORMED TYPE BARS <br />(EXCEPT #2 BARS) AND SHALL CONFORM TO THE REQUIREMENTS OF THE "STANDARD <br />SPECIFICATION A.S.T.M. 615 GRADE 40". <br />3.1.12 THE SHOP DRAWINGS SHALL EXPLICITLY SHOW LOCATION OF DOWNSPOUTS, <br />GASOLINE VENT LINES, ETC., AS RELATED TO ANY AND ALL UTILITIES AND/OR <br />PIPING AT COLUMN LOCATIONS. ROOF DRAINS AND LEADERS SHALL BE DIRECTED <br />DOWN THE INTERIOR CANOPY COLUMN EXITING SIDE OF ISLAND FORM, LEVEL OR ABOVE <br />FINISH GRADE OF CONCRETE SIDE PAD ON DOWNHILL SIDE OF ISLAND. DOWNSPOUTS <br />SHALL BE 4" X 4" CONSTRUCTED OF 16 GA GALVANIZED METAL OF FREEZE -PROOF <br />OR OPEN -FACE DESIGN. STRAP TO CANOPY COLUMN AT 24" O.C. <br />3.1.13 INCLUDE IN DESIGN PROVISION FOR OVERFLOW DEVICE AT OPPOSITE CORNERS OR <br />CANOPY. <br />3.1.14 CONSTRUCTION NOT SPECIFICALLY INDICATED SHALL BE ACCOMPLISHED PER <br />MINIMUM REQUIREMENTS OF THE UNIFORM BUILDING CODE, LATEST EDITION. <br />3.1.15 IF THERE ARE ANY CONFLICTS BETWEEN LINES ON DRAWINGS AND GENERAL NOTES <br />OR WITH SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS GOVERN. <br />3.1.16 ANY DEVIATION FROM THE PLANS OR SPECIFICATIONS SHALL BE APPROVED BY <br />SOUTHLAND'S CONSTRUCTION REPRESENTATIVE. <br />V) <br />z <br />0 <br />a <br />U <br />U <br />a <br />DATE: 08SEP97 <br />PROJECT N0: <br />3439.10 <br />DRAWN: MSP <br />APPROVED: CL <br />DRAWING <br />FSP -4 <br />0 <br />m <br />0 <br />o <br />} <br />a <br />� <br />J <br />r <br />a <br />0 <br />z <br />� <br />o <br />a <br />w <br />U <br />a <br />I <br />N <br />w <br />0 <br />'L <br />U <br />F- <br />N <br />DATE: 08SEP97 <br />PROJECT N0: <br />3439.10 <br />DRAWN: MSP <br />APPROVED: CL <br />DRAWING <br />FSP -4 <br />