Laserfiche WebLink
the February 18, 1999 inspection report. (Note: at time of the February 18, 1999 <br />inspection the north east dispensers had not arrived) <br />4. California Code of Regulations (CCR), Title 23, Division 3, Chapter 16, section 2630 <br />(d): Ernie's General Store has failed to meet the New UST monitoring system <br />requirements by not conducting a monitoring equipment routine maintenance, service <br />checks and monitoring equipment certification annually in 2000, or 2001. <br />5. California Code of Regulations (CCR), Title 23, Division 3, Chapter 16 section 2632 <br />(d)(1)(A-G): Ernie's General Store has failed to submit a written monitoring <br />procedure by the March 4, 1999 compliance date. <br />6. CCR section 2632(2)(A)(B): Ernie's General Store has failed to submit a written <br />response plan procedure by the March 4, 1999 compliance date. <br />7. EHD has not received the Underground Storage Tank Installation Certification of <br />Compliance Form C. <br />Ernie's General Store was given tank certification and blue tags so the station could receive a <br />fuel drop prior to conducting the precision test. The certificate and blue tags were issued <br />with the understanding the items stated in the February 18, 1999 inspection report would be <br />addressed by May 4, 1999. <br />Because Ernie's General Stores newly installed UST's have never been in monitoring <br />compliance, Briggs submitted new A &B state forms to update computer records showing <br />the site is `out of compliance' as of March 23, 20001 <br />To Achieve Permit Compliance the following items must be addressed: <br />Financial responsibility must be submitted to EHD. <br />2. The monitoring system must be tested and certified operational. This test will include <br />the northwest dispenser systems. <br />3. <br />4. A Written Monitoring Procedure addressing the requirements of CCR section 2632 <br />(d)(1)(A-G) must be submitted to EHD. <br />4. A Written Response Plan addressing the requirements of CCR section 2632 <br />(d)(2)(A&B) must be submitted to EHD. <br />5. Owner/Operator must contact contractor and complete the UST Installation <br />Certificate of Compliance. <br />6. The monitoring system must have its' monitoring system tested and certified <br />annually. Notify EHD of the date and time of testing. <br />