a <br /> i <br /> Raymond von Flue [EH] <br /> From: Hootman,Cory@Waterboards <Cory.Hootman@waterboards.ca.gov> <br /> Sent: Tuesday, August 26, 2014 11:53 AM <br /> To: Raymond von Flue [EHj <br /> Cc: Fisher, Laura@Waterboards <br /> Subject: Line leak detector'requirements <br /> Ray <br /> You contacted me about a project that has been submitted to you for approval that is a UST system with a portion of its <br /> piping aboveground. Your concern was related to which portions of piping is require to be monitored by the line leak <br /> detector. Pursuant to Health and Safety Code 25290.1 (h) and California Code of Regulations 2636 (f)(2), underground <br /> pressurized piping shall be equipped with an automatic line leak detector. As long as all underground pressurized piping <br /> is monitored by the line leak detector the system is in compliance with UST statute and regulation relating to line leak <br /> detection. <br /> Cory Hootman,Water Resource Control Engineer . <br /> State Water Resources Control Board, Division of Water.Quality <br /> Underground Storage Tank Program, Leak Prevention Technical Unit <br /> 10011 Street, 15Th Floor <br /> Sacramento,CA 95814 <br /> Ph: (916) 341-5668 <br /> Fax: (916)341-5808 <br /> i <br /> i <br /> i <br />