JUL 15 2016 <br /> 3. PIPING SUMP TESTING t �' `11 ` `" <br /> Test Method Developed By: ❑ Sump Manufacturer M Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum M Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used:lncon Sump Tester Equipment Resolution: +/-0.002^ <br /> STP Sump#87+ STY Sump#89 STP Sump N 91 STP Sump#Diesel <br /> Sump Diameter: 42" 42" 42" 42" <br /> Sump Depth: 64" 63" 64" 63" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of <br /> Hi as Pi in Penetration: 14" 14" 14" 14" <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: 13" 13" 13" 14" <br /> Condition of sump prior to testing: Good Good Good Good <br /> Portion of Sump Tested' 2"above piping 2"above piping 2"above piping 2"above piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No SNA ❑Yes❑No MNA ❑Yes❑No MNA ❑Yes❑No MNA <br /> roduct and water 7* <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail-safe <br /> shutdown?* ❑Yes❑No M NA ❑Yes❑No MNA ❑Yes❑No MNA ❑Yes❑No MNA <br /> Was fail-safe verified to be <br /> o erational7. ❑Yes❑No MNA ❑Yes❑No MNA ❑Yes❑No MNA ❑Yes❑No MNA <br /> Wait time between applying <br /> Pressure/vacuum/water and starting 30 minutes 30 minutes 30 minutes 30 minutes <br /> test: <br /> Test Start Time: 10:48 am 12:34 pm 12:34 pm 12:34 pm <br /> Initial Reading(R,): 0.7043 3.2390 2.0196 3.1314 <br /> Test End Time: 11:03 am 12:49 pm 12:49 pm 12:49 pm <br /> Final Reading(Rp): 0.7040 3.2390 <br /> 2.0196 3.1313 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> Change in Reading(RF-114): 0.0003 None None 0.0001 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +1-0.002" <br /> Test Result: © Pass ❑ Fail El Pass ❑ Fail ® Pass 0 Fail ® Pass ❑ Fail <br /> Was sensor removed for testing? M Yes❑No❑NA M Yes❑No❑NA M Yes❑No❑NA M Yes❑No❑NA <br /> Was sensor properly replaced and <br /> verified functional after testin 7 M Yes❑No❑NA M Yes❑No❑NA M Yes❑No❑NA M Yes❑No❑NA <br /> COmments—(include information on repairs made prior to testing and recommended ollow up or ailed tests) <br /> Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work% <br /> v <br /> 'If the entire depth of the sump is not tested,specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) !!! <br /> i <br />