Laserfiche WebLink
u <br /> JUL 15 2016 <br /> 4. UNDER-DISPENSER CONTAINMENT(UDC)TESTIN <br /> Test Method Developed By: ❑ UDC Manufacturer ®industry Standard ❑ Professional ngineer <br /> ❑ Other(Spec) <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: Ineon Sump Tester Equipment Resolution: +/-0.002" <br /> UDC#1/2 UDC#3/4 s UDC#5/6 UDC#7/8 <br /> UDC Manufacturer: Environ Environ Environ Environ <br /> UDC Material: Poly Poly Poly Poly <br /> UDC the 31" 31" 31" 31" <br /> Height from UDC Bottom to Top 6" 6" 6" 6" <br /> of Highest piping Penetration: <br /> Height from UDC Bottom to 4„ 4" 4" 4" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testis Good Good Good Good <br /> Portion of UDC Tested 2"above piping 2"above piping 2"above piping2"above i in <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑No ®NA ❑Yes❑No ®NA El Yes[I No ®NA E]Yes[3 No ®NA <br /> roduct and water)? <br /> ater?� <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for f til- <br /> safe shutdown?* ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> Was fail-safe verified to be <br /> o emtional7* ❑Yes❑No ®NA 11Yes El No ONA ❑Yes❑No ONA ❑Yes No ONA <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test <br /> Test Start Time: 1:43 1:43 pin 1:43 pin 2:10 m <br /> Initial Readin (Ri): 7.8461 3.2430 19570 5.2201 <br /> Test End Time: 1:58 pro 1:58 vin 1:58 pin 2:25 pm <br /> Final Reading ): 7.8450 3.2427 1.9551 5.2209 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> Change in Reading RF-Pq : 0.0011 0.0003 0.0019 0.0008 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002" <br /> Test Result: ® Pass ❑Fail ® Pass ❑Fail © Pass ❑Fail ® Pass ❑Fail <br /> Was sensor removed for testing? O Yes❑No❑NA ®Yes❑No Q NA ®Yes❑No❑NA M Yes Q No❑NA <br /> Was sensor properly replaced and <br /> verified functional after testing? O yes❑No❑NA O Yes❑No❑NA ®Yes E]No❑NA ®Yes ElNo[INA <br /> Comments—(include information on repairs made prior to testing and recommended ollow-up or ailed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> i If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is`NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />