3.07 Acceptable Products - RED THREAD IiA Piping Secondary Containment Piping <br /> System as manufactured by NOV Fiber Glass Systems or <br /> engineered approved equal. SECTION 1 - Scope <br /> This section covers the use of fiberglass reinforced plastic <br /> SECTION 4 - Installation and Testing (FRP) pipe for fuel handling and fuel handling vent and vapor <br /> 4.01 Training and Certification - All joints installed or applications including gasoline, unleaded gasoline, gasoline/ <br /> constructed In the field shall be assembled by employees alcohol mixtures, bio-diesel and diesel that require secondary <br /> of the contractor who have been trained by the pipe containment. <br /> manufacturer. The pipe manufacturer or their authorized <br /> representative shall train the contractors employees in the SECTION 2- General Conditions <br /> proper joining and assembling procedures required for the <br /> project, including hands-on participation by the contractors 2.01 Cnnrdinatissn - Material furnished and work <br /> employees. Each bander shall fabricate one pipe-to-pipe performed under this section shall be coordinated with the <br /> and one pipe-to-fitting joint that shall pass the minimum related work and equipment specified under other sections, <br /> pressure test for the application as stated in Section 2.03 i.e.Valves, Flexible Connectors, Equipment. <br /> without leaking. <br /> Only bonders that have successfully completed the 2.02 Governing Standards -- Except as modified or <br /> pressure test shall bond pipe and fittings. Each bonder shall supplemented herein, all materials and construction methods <br /> carry a current manufacturer's proof of training card. shall comply with and be tested in accordance with the <br /> 4.02 Pine Installation- Pipe shall be Installed as specified following standards and teat methods: <br /> and indicated on the drawings. <br /> The piping system shall be installed in accordance with the Standards and Test Methods: <br /> manufacturer's current published installation procedures. UL971 Standard for Nonmetallic Underground Piping for Flam- <br /> 4.03 Testing - A hydrostatic pressure test shall be 2004 enable liquids <br /> conducted on the completed piping system. The piping <br /> system shall be subjected to 10 pressurization cycles from 0 ASTM Standard Classification for Machine-Made'Fiberglass" <br /> psig to 1.5 times the design operating pressure as stated in D2310 (Glass Fiber Reinforced Thermosetting Resin)Pipe <br /> Section 2.03.c. After the 10 cycles,the pressure shall be held ASTM Standard practice for obtaining Hydrostatic or Pressure <br /> on the system for a minimum of 1 hour and the line Inspected D2992 Design Basis for"Fiberglass" (Glass Fiber Reinforced <br /> far leaks. Thermosetting Resin)Pipe and Fittings <br /> Test pressures shall not exceed 1.5 times the maximum <br /> rated pressure of the lowest rated element in the system. 2,03 Operating Conditions - In addition to the above <br /> All pipe joints shall be water tight. All joints that are found listed minimum design requirements, the system shall meet <br /> to leak, by observation or during testing, shall be replaced by the following minimum operating conditions: <br /> the contractor and retested. a. Operating Pressure <br /> Should hydrostatic testing be impractical, testing with b. Fluid Conveyed <br /> low pressure air or inert gas may be acceptable. Extreme c. Test Pressure <br /> caution should be used when testing with air. Follow all <br /> safety precautions and testing recommendations of the pipe 2.04 Quality Assurance - Pipe manufacturer's quality <br /> program shall be in compliance with ISO 9001 and/or API D1. <br /> manufacturer. <br /> 2.08 Deliverer Storage. and Handling - Pipe and fittings <br /> shall be protected from damage due to impact and point <br /> loading. Pipe shall be property supported to avoid damage <br /> due to flexural strain. The contractor shall not allow dirt, <br /> debris or other extraneous materials to get into pipe and <br /> fittings. All factory machined areas shall be protected from <br /> sunlight until installed. <br /> 2.06 Acceptable Manufacturers - NOV Fiber Glass <br /> Systems, 501-588-4010,or approved equal. <br />