• -6- • <br /> Veeder-Root ISD System Specifications <br /> TLS Console & ISD Software Version Number <br /> The presence of ISD and the ISD software version number can be verified on the TLS <br /> Console LCD screen by using the <STEP> key or by using the TLS Console <PRINT> <br /> key to print and review the latest ISD Daily Report. See Figure 213-10 and 213-11 for <br /> TLS and ISD verification instructions. <br /> The TLS Console must have a printer as well as an RS232 interface port. <br /> Operability Test Procedure <br /> The Veeder-Root ISD operability test procedure provided in Exhibit 9, and in section 4 <br /> of the ARB Approved Installation and Maintenance Manual for the Healy Phase // <br /> EVR System Including Veeder-Root ISD System, shall be used at GDF sites to <br /> determine the operability of the Veeder-Root ISD system to comply with applicable <br /> performance standards and performance specification in CP-201. Testing the ISD <br /> equipment in accordance with this procedure will verify the proper selection, setup and <br /> operation of the TLS Console sensors and interface modules. <br /> The Vapor Flow Meter <br /> The Veeder-Root ISD system requires one Vapor Flow Meter per dispenser installed via <br /> the ARB Approved ISD Vapor Flow Meter Manual 577013-796, Rev. E for the <br /> Veeder-Root ISD System. The Vapor Flow Meter shall be installed into dispensers <br /> listed in Exhibit 1 of this Executive Order in accordance with the ARB Approved <br /> Installation, Operation and Maintenance Manual for the Healy Phase lI EVR <br /> System Including Veeder-Root ISD System. The Vapor Flow Meter is an intrinsically <br /> safe sensor that is wired to the TLS Console Smart Sensor Module via a conduit <br /> dedicated to TLS Console low-voltage sensors. Figure 213-12 shows the ISD Vapor <br /> Flow Meter. Figures 213-16 and 2B-17 show the installation configuration. <br /> The Vapor Pressure Sensor <br /> The Veeder-Root ISD system requires one Vapor Pressure Sensor per GDF installed <br /> into one of the dispensers located closest to the tanks (If a row of dispensers are equal <br /> distance from the tank pad and within 10' of each other, any dispenser can be used) in <br /> accordance with the ARB Approved Installation, Operation and Maintenance <br /> Manual for the Healy Phase 11 EVR System Including Veeder-Root ISD System. <br /> The Vapor Pressure sensor shall be installed into dispensers listed in Exhibit 1 of this <br /> Executive Order. The Vapor Pressure Sensor is an intrinsically safe sensor that is <br /> wired to the TLS Console Smart Sensor Module via a conduit dedicated to TLS Console <br /> low-voltage sensors. Figure 213-13 shows an ISD Vapor Pressure Sensor illustration. <br /> Figures 213-16 and 213-17 show the installation configuration. <br /> Healy Phase 11 EVR System Including Veeder-Root ISD, Exhibit 2—VR-202-A <br />