Laserfiche WebLink
SWRCB, January 2002 <br />C <br />0 Page S of -71— <br />" irmmi `U "1rQ1D1 NQrD d"nWTAiNMTi.NT ITTDC'1 TESTING <br />/. V1\LL' l�-L11J1 L/a�viJa� vvi +a++..+•_�� • — -- — -- <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Equipment Resolution: .002 <br />a 3. <br />UDC # 1&2/ UDC # 3&4 <br />UDC # <br />iJDC # <br />UDC Manufacturer: Bravo <br />Bravo <br />UDC Material: Coated Steel <br />Coated Steel <br />UDC Depth: 10" <br />10" <br />Height from UDC Bottom to Top See Comments <br />See Comments <br />of Highest Piping Penetration: <br />Height from UDC Bottom to See Comments <br />See Comments <br />Lowest Electrical Penetration: <br />Condition of UDC prior to Dry <br />Dry <br />testin : <br />Portion of UDC Tested Water Lever 8" <br />Water Level 8" <br />Does turbine shut down when <br />UDC sensor detects liquid (both Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes No ❑ NA <br />Yes No ❑ NA <br />product and water)?* <br />Turbine shutdown response time NA <br />NA <br />Is system programmed for fail- X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />safe shutdown?' <br />Was fail-safe verified to be Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes No ❑ NA <br />Yes No ❑ NA <br />operational?* <br />Wait time between applying 5 Minutes <br />5 Minutes <br />water and starting test <br />Test Start Time: 9:15 <br />10:10 <br />Initial Reading (R,): .001 <br />.001 <br />Test End Time: 9:45 <br />10:40 <br />Final Reading (RF): .001 <br />.001 <br />Test Duration: 30 Minutes <br />30 Minutes <br />Change in Reading (RF -R,): 0 <br />0 <br />Pass/Fail Threshold or Criteria: .005/30 Minutes <br />.005/30 Minutes <br />Test Result: X Pass ❑ Fail <br />X Pass ❑ Fail <br />Pass ❑ Fail <br />Pass ❑ Fail <br />Was sensor removed for testing? X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />Was sensor properly replaced and X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />Yes ❑ No ❑ NA <br />verified functional after testing? <br />_Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />All penetrations enter from bottom of Bravo System UDC's. <br />t If the entire depth of the UDC is not tested, specify how much was tested. If the answer to gny of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />