Page 3 of 6 <br /> 8. MONITORING PLAN: (CoynN JED) <br /> b. Tank Annular Space Monitor: This monitoring probe is located inside the annular <br /> space between primary and secondary container. Its function is to detect the <br /> presence of liquid in the secondary container. Should any liquid be detected, an <br /> audible and visual alarm will alert the Owner of a potential leak either from the <br /> primary to the secondary container or ground water intrusion into the secondary <br /> container. <br /> c. Monitoring of Sacrificial Anode: The sacrificial anode will be monitored by <br /> measuring tank to soil voltage. Tank to soil potential readings will be taken <br /> with a high impendance voltmeter and a copper/copper sulfate reference electrode <br /> placed immediately above the underground tank. A reading less than -850 <br /> millivolts indicates the tank is protected. When reading exceeds 'SAFE' , the <br /> sacrificial anode will be replaced and tank inspected and tested as required. <br /> d. Sub-pump and Tank Riser Monitor: This monitoring probe is located inside the <br /> containment box surrounding the tank suhnersible pump. Its function is to detect <br /> the presence of liquid in the Secondary Container. Should any liquid be detected, <br /> an audible and visual alarm will alert the Owner of a potential leak frcan the sub- <br /> pump <br /> e. Piping Secondary Contaiment Monitor: This monitoring probe is located inside the <br /> containment box surrounding the sub-pump. Its function is to detect the presence <br /> of liquid in the containment box which could indicate a leak in the product <br /> piping. If any liquid is detected, an audible and visual alarm will alert the <br /> Owner of a potential leak. <br /> f. Pressurized piping systems shall be monitored utilizing in line leak detectors, <br /> located in sub-pump piston leak detection. Operator is to be aware that reduction <br /> in product flow to 3 + gallons per minute indicates a potential leak. Leak <br /> detectors will be tested twice a year for proper operation. <br /> g. Records and Inspections - All records of underground tanks and petroleum piping <br /> shall be logged in writing using corresponding inspection log. Following is a <br /> list of monitoring activities and inspection which will be recorded. <br /> 1. Weekly records and visual inspections shall be made of: <br /> - Submerged Pump Boxes <br /> - Fill Boxes (also inspected after each delivery) <br /> - Reconcilation of the inventory control records <br /> h. Emergency Response Procedure: <br /> Once the operator is aware of a potential leak he shall: <br /> - Shut the system down using pinup shut-off switch <br /> - Attempt to isolate leak location by inspection <br /> - Contact the City of Lodi Fire Department <br /> - Record the leak with the action taken on the recordable discharge log <br /> (Incident shall be signed by the responsible representative) . <br />