Laserfiche WebLink
SANJOAQUIN Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GAS DEPOT#2 1330 E YOSEMITE AVE, MANTECA December 28, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 211 CCR 2715(c)(2) No employee present that were trained in the operation and maintenance of the UST system by a <br /> DO. <br /> The designated operator employee training for Kevin Hur was not performed using the correct form. The <br /> designated operator shall train facility employees for which he or she is responsible in the proper operation and <br /> maintenance of the UST system once every 12 months. The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br /> the training records to the EHD. <br /> Training performed after OCtober 1 st,2018 shall be recorder using the UNDERGROUND STORAGE TANK <br /> FACILITY EMPLOYEE TRAINING CERTIFICATE found in title 23 chapter 16 appendix XII. <br /> This is a Class II violation. <br /> 318 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gallons per hour leak at 10 pounds per square inch. <br /> The 87 product VMI line leak detector failed to detect a leak when tested. All line leak detectors shall be capable of <br /> detecting a 3-gallon per hour leak at 10 psi. The service technician adjusted the leak detector, retested it, and it <br /> passed. <br /> This is a repeat violation, Class II. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> Owners or operators of underground storage tanks that do not meet California Code of regulations,title 23 division <br /> 3, chapter 16 section 2635(c)(2)shall test overfill prevention equipment once by October 13th, 2018 and every 36 <br /> months thereafter; and within 30 days of the date of a repair.The site did not performed the testing by October 13th, <br /> 2018 however the service technician on site was able to conduct the overfill prevention equipment inspection today <br /> (12/28/18)while the inspector was on site. Ensure to conduct overfill prevention equipment inspection within the <br /> time frame provided by the regulation and submit test results within 30 days of performing the inspection. Ensure a <br /> 48 hour notification is provided to EHD prior to conducting the inspection <br /> This is a Class II violation. <br /> FA0012355 PR0515864 SCO01 12/28/2018 <br /> EHD 23-01 Rev.09/28/2018 Page 6 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />