Laserfiche WebLink
8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested- ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +,i- 0.002" <br />Fill Sump # 91 <br />Fill Sump # Diesel 81 <br />42" <br />Sump Diameter: <br />42" <br />42" <br />Sump Depth: <br />68" <br />66" <br />68" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />N/A <br />N/A <br />N/A <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />20" <br />20" <br />18" <br />Condition of sump prior to <br />testing: <br />Good <br />Good <br />Good <br />Portion of Sump Tested <br />2" above piping <br />2" above piping <br />2" above piping <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 minutes <br />30 minutes <br />30 minutes <br />Test Start Time: <br />9:19 am <br />9:46 am <br />10:11 am <br />Initial Reading (R,): <br />3.9142 <br />3.9265 <br />7.2823 <br />Test End Time: <br />9:35 am <br />10:01 am <br />10:26 am <br />Final Reading (RF): <br />3.9142 <br />3.9268 <br />7.2824 <br />Test Duration: <br />16 min. <br />15 min. <br />15 min. <br />Change in Reading (RF -RI): <br />0.0000 <br />0.0003 <br />0.0001 <br />Pass/Fail Threshold or Criteria: <br />+/-0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />O Pass ❑ Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work <br />