6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer ® industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />'fest Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/- 0.002" <br />Sump Diameter: <br />Sump Depth: <br />Sump Material: <br />Height from Tank Top to Top of <br />Highest Piping Penetration: _ <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />Condition of sump prior to testing: <br />Portion of Sump Tested' <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?* <br />Turbine shutdown response time <br />Is system programmed for fail-safe <br />shutdown?* <br />Was fail-safe verified to be <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />Test Start Time: <br />Initial Reading (Rj): <br />Test End Time: <br />Final Reading (RF): <br />Test Duration: <br />Change in Reading (RF-Ri): <br />Pass/Fail Threshold or Criteria: <br />Test Result: <br />Was sensor removed for testing? <br />Was sensor properly replaced and <br />venfied functional after testing? <br />STP Sump # 87 <br />42" <br />66" <br />Fiberglass <br />18" <br />16" <br />Good <br />2" above Divine <br />STP Sump #9I <br />42" <br />66" <br />Fiberglass <br />26" <br />18" <br />Good <br />2" above piping <br />STP Sump # Diesel <br />42" <br />65" <br />Fiberglass <br />24" <br />18" <br />Good <br />2" above piping <br />❑ Yes ❑ No ® NA 1 ❑ Yes ❑ No ® NA 1 ❑ Yes ❑ No ® NA <br />N/A <br />N/A <br />N/A <br />❑ Yes ❑ No ®NA I ❑ Yes ❑ No ®NA ( ❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA I ❑ Yes ❑ No ®NA I ❑ Yes ❑ No ®NA <br />30 minutes <br />11:17 am <br />5.9721 <br />11:33 am <br />5.9720 <br />16 min. <br />0.0001 <br />+/- 0.002" <br />I@ Pass ❑ Fail <br />® Yes ❑No❑NA <br />® Yes ❑No❑NA <br />30 minutes <br />10:33 am <br />1.6170 <br />10:48 am <br />1.6165 <br />15 min. <br />0.0005 <br />+/- 0.002" <br />L7 Pass ❑ Fail <br />® Yes ❑No❑NA <br />® Yes ❑No❑NA <br />30 minutes <br />10:33 am <br />5.1319 <br />10:48 am <br />5.1316 <br />15 min. <br />0.0003 <br />+/- 0.002" <br />® Pass ❑ Fail <br />• Yes ❑No❑NA <br />® Yes ❑No❑NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />If the entire depth of the sump is not tested, specify how much was tested. If the answer to as of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />