Laserfiche WebLink
10. SPILL/OVERFILL CONTAINMENT ROXFR' <br />Facility is Not Equipped With Spill/Overfill Containment Bores ❑� <br />Spill/Overfill Containment Boxes are Present, but ,,vere Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ®Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br />Vapor Spill Box # 87 Vapor Spill Box # 91 <br />Bucket Diameter: <br />12" <br />12" <br />Bucket Depth: <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and <br />10 min. <br />10 min. <br />starting test: <br />_ <br />Test Start Time: <br />11:42 am <br />11:42 am <br />Initial Reading (Rj): <br />6.8737 <br />4.8707 <br />Test End Time: <br />11:57 am _ <br />11:57 am <br />Final Reading (RF): <br />6.8742 <br />4,8720 <br />Test Duration: <br />15 min. <br />15 min. <br />Change in Reading (Rr-RJ): <br />0.0005 <br />0.0013 <br />Pass/Fail Threshold or <br />Criteria: <br />+/-0.002" <br />+/-0.002" <br />Test Result: <br />® Pass 0 Fail <br />© Pass 0 Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />