S WRCB,January 2002 Page—I--of (P <br /> 6--.PIPING SUMP TESTING <br /> Test Method Developed By: ❑Smnp Manufacturer 3 Industry Smude d X ProhDss�onsl Engineer <br /> 0 Other(Specify) <br /> Test Method Used: D Pressure 0 Vacuum XHydrostatic <br /> 7 Other(specify) <br /> Test Equipment Used: Caldwell Systems Equipment Resolution: .005/30 min <br /> Sump#1 Sump 9 2 Sump## Sump 0 <br /> Sump Diameter: 48" 48" <br /> Sump Depth: 62" 62" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to'Top of 1353 14" <br /> Hi est Pipilig Penetration: <br /> Height from Tank Top to Lowest 22" 3N, <br /> Electrical Peneration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' 2"above Highest piping pews ation <br /> Does turbine shut down when <br /> sump sensor detects liquid(both x Yes ❑No O NA x Yes 0 N 0-NA ❑Yes ❑No 0 N 0 Yes ❑No --NA <br /> product and water 1, <br /> Turbine shutdown response time <br /> is system propwwned for fail-safex Yes 13 No O NA x Yes 0 N 0 NA [IYes DNo DNA j 0 Yrs [INo JNA <br /> shutdown? <br /> Was fail-safe verificd to be ❑'Yes x No ❑NA C Yes x No CNA ❑Ycs DNo ❑NA i D Yes []No ❑NA <br /> opex- ationat?' <br /> Wait-time between applying <br /> pressurefvacoum/water and stating 5 min 5 min 5 min 5min <br /> test: <br /> Test Start Time: 10:00 9:17 <br /> Initial Reading(Ru): .00" t10" .00, .00" <br /> Test End Time: 2030 9:47 <br /> Final Reading(RF): .00 .00 1 <br /> Test Duration_ 30 min 130 min 30 min 30 min <br /> Change in Reading(R+-RD: .00 00 <br /> PasvFail Threshold or Criteria: -005/30 mien 005/30 min 005/30 min 00S/30 rutin <br /> Test Result: x Pass ❑Fail x Pass C3 Fail ❑ Pass ❑Fild ❑ P'ass ❑F W <br /> Was sensor removed for testing? x Yes D No ❑NA x Yes ❑No 0 NA x Yes ❑No ❑NA C~Yes ❑No 0 NA <br /> Was sensor properly replaced and x Yes C)No I--]NA xYes 0 N 11 NA x Yes. El No DNA C Yes d No .DNA <br /> verified functional after testis . <br /> Comments (include in or�satlon on re airs made for to testis , and recommended follow-u or ailed rests) <br /> 1 If the entire depth of the sump is not Tested,specify how much was tested. 1f the answer to ME of the questions indicated with an <br /> asterisk(4)is"NO" or"NA",the entire sump must be tested. (See SWRCB LG-160) <br /> V-d 966O-VVL-60Z 1S31bYQb0-�z1d dZt7:Z6 O6Zbgej <br /> ]00 •d 80I000860Z i 'ON XVJ SS31 WO QOOH NV H :20 HV0 i0Z/00/M <br />