Laserfiche WebLink
SWRCB , January 2002 Page of <br /> 8. PIPING SUMP TESTING <br /> Test Method Developed By : ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br /> ❑ Other (Spec) <br /> Test Method Used : ❑ Pressure ❑ Vacuum X Hydrostatic <br /> ❑ Other (Spec) <br /> Test Equipment Used : Caldwell Level Change Indicator Equipment Resolution : . 002 <br /> Sump # 5-Diesel Sump # 6-Race 100 Sump # Sump # <br /> Sump Diameter: 42" 42" <br /> Sump Depth : 29" 231/2 <br /> Sump Material : Fiberglass Fiberglass <br /> Height from Tank Top to Top of Vent 16" Vapor/Vent 13 " <br /> Highest Piping Penetration : Product 5 " Product 5 " <br /> Height from Tank Top to Lowest 17" 9" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested ' Water Level 21 " Water Level 19" <br /> Does turbine shut down when <br /> sump sensor detects liquid (both Yes Yes <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe Yes Yes <br /> shutdown? * <br /> Was fail -safe verified to be No No <br /> operational ?* <br /> Wait time between applying water 5 Minutes 5 Minutes <br /> and starting test : <br /> Test Start Time : 10 : 42 10 : 37 <br /> Initial Reading (RI) : . 001 . 001 <br /> Test End Time : 11 : 12 11 : 07 <br /> Final Reading (RF) : . 001 . 001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading (RF-RI) : 0 0 <br /> Pass/Fail Threshold or Criteria: . 005/30 Minutes . 005/30 Minutes <br /> Test Result. Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' If the entire depth of the sump is not tested, specify how much was tested . If the answer to anv of the questions indicated with an <br /> asterisk ( * ) is "NO" or "NA", the entire sump must be tested . ( See SWRCB L& l60) <br />