. SIA No. 3 —Moisture Separator High-Level Shutoff Switch (HLS-201) <br /> Water entrained in the vapor recovery stream will be collected in the Moisture Separator <br /> (S-201) If the water level in this vessels approaches its capacity, this interlock (designated as <br /> SAI No 3 on the PFD) will shut off the SVE Blower If this interlock is triggered, the SVE <br /> Blower will shut down and will, in turn, shut down the rest of the operations The system will <br /> remain off until the fluids are removed from the separator and the system is manually reset <br /> SIA No. 4—SVE Blower High-Temperature Switch (TSH-201) <br /> The exhaust stream from the SVE blower(C-201) will need to remain below 225°F to avoid <br /> damage to the equipment If the exhaust temperature from C-201 exceeds the set point, this <br /> interlock(designated as SAI No 4 on the PFD) will shut off the SVE Blower The system will <br /> remain off until manually reset Upon reset the cause for the temperature excess will be <br /> investigated <br /> SIA No. 5—ICE Unit High-Temperature Switch (TSH-301) <br /> The operating temperature of the ICE unit engine must remain within safe operating conditions <br /> If the engine temperature exceeds a pre-set level, this interlock (designated as SAI No 5 on <br /> . the PFD) will shut off the ICE Unit and the SVE System The SVE and vapor treatment <br /> systems system will remain off until manually reset Upon reset the cause for the overheating <br /> engine will be investigated <br /> SIA No. 6--Low-Oil Switch (OSL-301) <br /> The lubricating oil for the ICE unit engine must remain be maintained at sufficient levels for <br /> safe operation of the unit If the engine oil gets below a pre-set level, this interlock(designated <br /> as SAI No 6 on the PFD) will shut off the ICE Unit and the SVE System The SVE and vapor <br /> treatment systems system will remain off until manually reset Upon reset, the remaining oil <br /> will be drained from the unit and new lubricating oil will be utilized to fill the reservoir <br /> Potential leaks will be thoroughly investigated <br /> Important Note. The SVE System may operate without the AS System,but the AS System may not <br /> operate without the SVE System Therefore, SAI 2 will shut down only the AS operations, but SAIs <br /> 3, 4, 5, and 6 will shut down both systems <br /> The SAIs are presented on the PFD (Figure 13) Each SAI is represented with a diamond and has <br /> a unique number designation Details of the supporting control equipment is presented on the P&ID <br /> (Figure 14) <br /> V-5 <br />