Laserfiche WebLink
Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />Fpiping Run # 87 <br />Piping Run # 91 <br />Piping Material: <br />Fiberglass <br />Fiberglass <br />Piping Manufacturer: <br />Smith <br />Smith <br />Piping Diameter: <br />3" <br />3" <br />Length of Piping Run: <br />100' <br />100' <br />Product Stored: <br />Gasoline <br />Gasoline <br />Method and location of <br />piping -run isolation: <br />Reducer Boots/ Fittings <br />Reducer Boots! Fittings <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />JJ <br />Test Start Time: <br />12:00 pm <br />1:00 pm <br />- w <br />4, <br />Initial Reading (Rj): <br />5 psi <br />5 psi <br />Test End Time. <br />1:00 pm <br />2:00 pm <br />L <br />Final Reading (RF): <br />5 psi <br />5 psi <br />'T'est Duration: <br />1 hour <br />1 hour <br />g s <br />Change in Reading (RF -R,): <br />None <br />None <br />Pass/Fail Threshold or <br />Criteria: <br />No Detectable Loss <br />No Detectable Loss <br />Test Result: <br />O Pass 0 Fail <br />[R] Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up fbr failed tests) <br />Both secondary lines were leaking from bravo hubs. Tightened hubs and re -tested lines. Lines stopped leaking. <br />a <br />