Laserfiche WebLink
SWRCB, January 2002 <br />0 Page of <br />Test Method Developed By: X Piping Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: X Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Pressure Gauge <br />Equipment Resolution: 0-15 PSI <br />,...... ...,.. , t��,:...,�i.�tssis;,tv:._=�. �; �.;"��k',�� <br />_.. ;.. .'�` .:;;..:.'^4',t..�� <br />:•, •'N �'v`. •tr,t""9w..a���•..«'�..,^�,y <br />gcs,,^€;��� .�; x%�4;, t�.#�.g: <br />Piping Run # 1 <br />Piping Run # 2 <br />Piping Run # <br />Piping Run # <br />Piping Material: Fiberglass <br />Fiberglass <br />Piping Manufacturer: Smith <br />Smith <br />Piping Diameter: 3" <br />3" <br />Length of Piping Run: 200' <br />200' <br />Product Stored: Diesel <br />Diesel <br />Method and location of Test boot <br />piping -run isolation: <br />Test boot <br />Test boot <br />Test boot <br />Wait time between applying <br />pressure/vacuum/water and 5 min <br />starting test: <br />5 min <br />5 min <br />5 min <br />Test Start Time: 8:55 <br />8:55 <br />Initial Reading (RI): 5 PSI <br />5 PSI <br />Test End Time: 9:25 <br />9:25 <br />Final Reading (RF): 5 PSI <br />5 PSI <br />Test Duration: 30 min <br />30 min <br />30 min <br />30 min <br />Change in Reading (RF -R,): 0 <br />0 <br />Pass/Fail Threshold or 0 drop <br />Criteria: <br />0 drop <br />0 drop <br />0 drop <br />Test Result: % Pass ❑ Fail <br />% Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />