Site Preparation and Installati nstructions <br />EMC UST Monitoring System <br />WEATHERPROOF <br />JUNCTION BOX <br />(t PER PROBE) <br />t/2" RIGID <br />CONDUIT i glk <br />• <br />TO FROM <br />MONITOR PROBE <br />• <br />+ Wht <br />Figure 34. Two -Wire Probe Field Wiring Installation Diagram. <br />7. Carefully lower probe into the riser pipe until the boot <br />rests on the bottom of the tank. <br />10 CAUTION: DO NOT ALLOW PROBE TO FREEFALL <br />AND/OR SHARPLY IMPACT THE BOTTOM OF THE <br />TANK. SHOCK TO THE PROBE FOOT WILL RESULT IN <br />SEVERE PROBE DAMAGE. <br />8. Feed the two -wire probe cable (furnished with each <br />probe) up through the cap bushing and in through the <br />junction box bushing. Leave enough slack in the cable <br />between the cap and junction box to allow the cap to <br />easily reach the riser pipe. In addition, leave enough slack <br />under the riser cap to permit connection to the probe and <br />to allow the probe to rest on the bottom of the tank. <br />9. Using wiring nuts, connect the wires from the probe cable <br />to the probe field wires in the junction box (see Figure 34, <br />I'wo-Wire Probe Field Wiring Installation Diagram"). Be <br />sure to observe proper polarity between the probe and <br />monitor wiring during installation. The conduit must be <br />properly sealed in accordance with the National Electrical <br />Code (NFPA 70) and the Automotive and Marine Service <br />Station Code (NFPA 30A) since they pass from a Class I, <br />Division I or Division II area into a non -hazardous area. <br />"`I NOTE: SEAL WIRE NUT CONNECTIONS AT THIS <br />TIME USING epoxy sealant, furnished with each probe. <br />WARNING: EPDXY SEALANT MAYBE IRRITATING <br />TO EYES AND SKIN. MAY CAUSE SKIN SENSITI- <br />ZATION IN SUSCEPTIBLE INDIVIDUALS. MAY BE <br />ABSORBED THROUGH THE SKIN. EPDXY SEAL- <br />ANT CONTAINS EPDXY RESIN AND VINYL CYCLO - <br />HEXENE DIOXIDE. VINYL CYCLOHEXENE DIOX- <br />IDE HAS CAUSED SKIN CANCER IN ANIMAL <br />TESTS. <br />PRECAUTIONS: AVOID EYE AND SKIN CONTACT. <br />WEAR IMPERVIOUS GLOVES AND SAFETY GLAS- <br />SES. USE ONLY IN WELL VENTILATED AREAS. <br />10. Tighten the cable bushing nuts on the probe riser cap and <br />junction box to ensure a water -tight seal at the probe <br />cable entry. <br />11. Secure the riser locking cap to the top of the riser pipe. A <br />padlock may be installed for added security. <br />SECTION 7. INTERSTITIAL LIQUID SENSOR <br />INSTALLATION <br />A. EQUIPMENT PREPARATION. <br />,114 WARNING: TO AVOID ELECTRICAL SHOCK WHICH <br />COULD KILL YOU, BE SURE AC POWER TO THE <br />MONITOR IS OFF DURING INSTALLATION. <br />1. Turn OFF power to the EMC system. <br />,t NOTE: Do not install the sensor if any liquid is present <br />"® in the annular space. Failure to comply will lead to an <br />alarm. <br />2. Make sure no liquid is present in the annular space. <br />22 <br />B. INSTALLATION OF FLOAT SWITCH — <br />STEEL TANKS. <br />1. To be sure the sensor will reach the bottom of the annular <br />space, first measure the sensor riser pipe from the bottom <br />of the pipe to the top. Then measure the same distance up <br />the leader cable from its connection to the sensing ele- <br />ment and mark the leader cable. <br />16 CAUTION: DO NOT USE A KNIFE OR OTHER SHARP <br />OBJECT TO MARK THE LEADER CABLE. MARK THE <br />DISTANCE WITH A MARKER, TAPE, OR A TWIST TIE. <br />2. Lower the float switch assembly into the riser pipe until <br />the float switch touches the bottom of the tank (see Figure <br />35, "Float Switch Installation — Steel Tanks"). <br />3. Keeping the cable taut, secure the sensor assembly in <br />place by attaching the grip cord. <br />NOTE: The float switch assembly must not hang by the <br />"r cable, but should rest lightly on the bottom of the tank <br />supported by the cable. <br />4. Secure the riser cap to the riser pipe. <br />5. Tighten the cable bushing nuts on the riser cap and junc- <br />tion, box to ensure a water -tight seal at the cable entry. <br />Figure 35. Float Switch Installation — Steel Tanks. <br />6. Using wire nuts, connect the two -wire sensor cable to the <br />field wires in the sensor junction box (see Figure 36, "Two - <br />Wire Sensor Field Wiring Diagram"). Since these are <br />contact switches, polarity is not a consideration when <br />connecting sensor wires to field wires. <br />'�.I NOTE: SEAL WIRE NUT CONNECTIONS AT THIS <br />® TIME USING epoxy sealant, furnished with each sensor. <br />