Laserfiche WebLink
6.PIPING SUMP TESTING <br /> Test Method Developed By: r Sump Manufacturer Industry Standard r Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure r Vacuum F Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> soon Sump Sump Sump Sump <br /> UE020U001 <br /> Sump Diameter: 40" <br /> Sump Depth: 45" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of <br /> Highest Piping Penetration: 14" <br /> Height from Tank Top to Lowest 14" <br /> Electrical Penetration: <br /> Condition of sump prior to Good <br /> testing : <br /> Portion of Sump Tested(1) 2" above piping <br /> Does turbine shut down when g� <br /> sump sensor detects liquid(both r'Yes r No's NA Yes ' No F' NA Yes No r NA r Yes r No f NA <br /> product and water)?* <br /> Turbine shutdown response time n/a <br /> Is system programmed for fail- � - — <br /> safe shutdown?* r Yes r No I_ NA r Yes r No r' NA g 1 Yes No 1} NA r Yes r No F NA <br /> Was fail-safe verified to be <br /> operational?* p9�r Yes! No NA r Yes r No NA r Yes dg Nor NA 1 Yes r Nor <br /> NA <br /> Wait time between applying <br /> pressure/vacuum/water and 30 min <br /> starting test: <br /> Test Start Time: 11:25 am 11:41 am <br /> Initial Reading(R,): 5.2484 5.2485 <br /> Test End Time: 11:40 am 11:56 am <br /> Final Reading(RF): 5.2485 5.2485 <br /> Test Duration: 15 min 115 min <br /> Change in Reading(R rR,): .0001 10 <br /> Pass/FaiI"Threshold or Criteria: 0.002 10.002 <br /> Test Result: F',Pass r Fail r Pass F Fail r Pass F Fail F Pass F Fail <br /> Was sensor removed for testing? Yes r No r ypp <br /> NA 1 Yes t No I NA r Yes r No r NA F Yes r No r NA <br /> Was sensor properly replaced and 9 <br /> verified functional after testing? r Yes d No <br /> NA r Yes yam- F p No 1 NA Yes r No I NA 4 Yes r Nor NA <br /> Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) T _, <br /> Reinstall sensor to lowest point but not tested. <br /> i <br /> i <br /> (1)If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated <br /> with an asterisk(*)is"NO"or"NA',the entire sump must be tested. (See SWRCB LG-160) <br />