0 <br /> PLC-5000 Site Controller, LD-2000 and LD-2000 PLC <br /> 4.0 Description of the Testing Location <br /> The Vaporless system was evaluated at the Fuels Management Research Center which <br /> is located in Grain Valley, Missouri and operated by Ken Wilcox Associates, Inc. All line <br /> tests were conducted using regular unleaded gasoline. The full evaluation was <br /> conducted on a 3.25 inch diameter, 200 ft. long fiberglass line. The capacity of the line <br /> is 86 gallons. The bulk modulus, which is a measure of the "stretch" which occurs <br /> when the line is pressurized, is 34,443 psi, which is within the guidelines specified by <br /> the EPA protocol. Abbreviated testing was conducted on a 215 ft. long flexible pipeline <br /> with a total volume of 19.7 gallons. The bulk modulus of the flexible pipeline is 4,485 <br /> psi. <br /> The conditioned product is contained in a 600 gallon steel tank which is equipped with a <br /> standard Red Jacket pump. Product is heated or cooled in the tank by circulating glycol <br /> and product through an external heat exchanger. Soil temperatures were monitored at <br /> approximately the mid distance between the tank and the dispenser. RTI)s were <br /> located at 2 inches, 4 inches and 12 inches from the line as specified by the protocol. A <br /> single temperature probe was located 4 inches from the bottom of the product <br /> conditioning tank. The weighted soil temperature and the product tank temperature at <br /> the beginning of the test were used to compute the temperature differential. <br /> Page 5 <br />