Tank 411-11D This 10 ,000 gallon diesel tank and piping system <br /> showed a product volume loss greater than -0.055 gal/hour. A low <br /> • level Horner test of the "tank only" showed the tank to be "pro- <br /> duct tight" within the acceptable compliance limits. The conclu- <br /> sion reached is a likely leak in the piping system. It may be <br /> possible to line test the product delivery pipe, if the check <br /> valve does not leak. A product line pressure test is recom- <br /> mended. <br /> Tank 490-41D This 2 ,000 gallon diesel tank and piping system <br /> was tested by both the PETRO TITE and Horner EZY-CHECK methods . <br /> The PETRO TITE conducted first showed a product volume loss of <br /> -0.354 gal/hour. The Horner low level test of the "tank only" <br /> showed the tank "product tight" with a result of -0.004 gal/hour. <br /> • A product line pressure test is recommended. <br /> Site 300 Facility <br /> Tank 815-11D This 10,000 gallon diesel tank and piping system <br /> was tested by the Horner EZY-CHEK method and showed a product <br /> volume gain greater than 0.02 gal/hour . This result is inconclu- <br /> sive and indicates unsatisfactory test conditions, such as : pro- <br /> duct line check valve leaking product into the tank, groundwater <br /> leaking into the tank, or a vapor pocket expanding during the <br /> test . A standpipe test procedure can, in some cases , overcome <br /> the influence of the above conditions. <br /> -9- <br />