Laserfiche WebLink
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />April 10, 2019 <br /> Facility Address: <br /> 14000 E HWY 88 , LOCKEFORD <br /> Facility Name: <br /> H&S Energy Products,#3038 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 208 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br />The designated operator failed to document all the alarms from the attached alarm history on the 3/28/19 <br />designated operator monthly inspection report and failed to check that they were responded to appropriately. The <br />missing alarms include: L7: UDC 1/2 sensor out, set up warning and sensor out alarm on 3/17/19. During the <br />designated operator inspection, the designated operator shall review the alarm history for the previous month, check <br />that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br />documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br />inspections at least once every 30 days at this facility and are including all of the required information on the reports. <br />This is a repeat violation, Class II. <br /> 210 CCR 2715(c) No employee present that were trained in the operation and maintenance of the UST system by a DO. <br />The designated operator employee training for Molly Sullivan was not current. Molly was las trained on 3/13/18 and <br />is a month overdue. The designated operator shall train facility employees for which he or she is responsible in the <br />proper operation and maintenance of the UST system once every 12 months. The training shall include, but is not <br />limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility’s best management practices <br /> 2. Employee’s role with regard to monitoring equipment as specified in the facility’s monitoring plan <br /> 3. Employee’s role with regard to spills and overfills as specified in the facility’s response plan <br /> 4. Name of the contact person(s) for emergencies and monitoring equipment alarms <br />Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br />the training records to the EHD. <br />This is a Class II violation. <br />FA0000091 PR0231631 SC001 04/10/2019 <br />EHD 23-01 Rev. 9/16/2020 Underground Storage Tank Program OIRPage 5 of 8 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD