Laserfiche WebLink
eco' <br /> Page 5 of 9vt <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ®Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Level Change Indicator Equipment Resolution: 0.0025 <br /> Sump#87 Sump#87 SYP Sump#91 Sump#Vent Box <br /> Su np Diameter: 42 in 42 in 42 in <br /> Sump Depth: 36 in 33 in 31 in 24 in <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 15 in 17 in 14 in 18 in <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 13 in 14 in 11 in 12 in <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' 2°above prod.piping 2"above prod.piping 2"above prod.piping 2°above prod.piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No®NA <br /> product and water)?* <br /> Turbine shutdown response time See comments See comments *See comments See comments <br /> Is system programmed for fail-safe <br /> shutdown?; ❑Yes -]No®NA ❑Yes -]No®NA ❑Yes❑No❑NA -]Yes❑No®NA <br /> Was fail-safe verified to be <br /> ❑� <br /> operational?* es❑ ❑ ❑ ❑ ❑ ❑ <br /> No®NA Yes No®NA Yes No®NA Yes❑No®NA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5 min 5 min 5 min 5 min <br /> test: <br /> Test Start Time: 2:00 PM 1:20 PM 1:50 PM 2:25 PM <br /> Initial Reading(R,): 0 0 0 0 <br /> Test End Time: 2:30 PM 1:50 PM 2:20 PM 2:55 PM <br /> Final Reading(RF): 0 0 0 0 <br /> Test Duration: 30 min 30 min 30 min 30 min <br /> Change in Reading(Rr-Ri): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: 0.0025 0.0025 0.0025 0.0025 <br /> Test Result: N Pass ❑Fail E Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No RNA ®Yes❑No[-INA ®Yes[-]No[-INA <br /> Was sensor properly replaced and <br /> verified functional after testing? ®Yes[:]No❑NA ®Yes[-]No❑NA ®Yes❑No[_]NA ®Yes[-]No[:INA <br /> Comments- (include information on repairs made prior to testing, and recommended folloii,,-up for failed tests) <br /> * Sump(s) sensor(s)were tested separately as part of the annual monitor certification test. <br /> i <br /> If the entire depth of the sump is not tested.specify how much was tested. If the answer to anN,of the questions indicated with an <br /> asterisk (*)is"NO"or`NA the entire sump must be tested. (See SWRCB LG-160) <br />