Laserfiche WebLink
Page 6 of 9 eco <br /> 7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Level Change Indicator Equipment Resolution: 0.0025 <br /> UDC#1-2 UDC#3-4 UDC#5-6 UDC# <br /> UDC Manufacturer: Unknown Unknown Unknown <br /> UDC Material: Fiberglass Fiberglass Fiberglass <br /> UDC Depth: 30 in 30 in 30 in <br /> Height from UDC Bottom to Top 12 in 12 in 12 in <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 5 in 5 in 5 in <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested' 2"above prod.piping 2"above prod.piping 2"above prod.piping <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes[-]No®NA ❑Yes❑No®NA ❑Yes ❑No❑NA <br /> product and water)?" <br /> Turbine shutdown response time See comments See comments See comments <br /> Is system programmed for fail- <br /> safe shutdown? ❑1 es❑No®NA ❑Yes❑No®NA [-]Yes❑No®NA <br /> Was fail-safe verified to be <br /> operational? ❑Yes❑No®NA [:]Yes[-]No®NA ❑Yes❑No®NA <br /> Wait time between applying 5 min 5 min 5 min <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 1:00 PM 1.05 PM 1:10 PM <br /> Initial Reading(Rj): 0 0 0 <br /> Test End Time: 1:30 PM 1:35 PM 1:40 PM <br /> Final Reading(RF): 0 0 0 <br /> Test Duration: 30 min 30 min 30 min <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass/Fail Threshold or Criteria: 1 0.0025 0.0025 0.0025 <br /> Test Result: Pass ❑Pail M Pass ❑ Fail Z Pass ❑ Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? ®Yes❑No DNA ❑Yes❑No[INA ®Yes❑No[:INA ❑Yes❑No[:INA <br /> Was sensor properly replaced and ❑Yes❑No DNA ®Yes[-]No DNA ®Yes [:]No❑NA [-]Yes❑No DNA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recoinmended,follow-up.for.failed tests) <br /> * UDC sensor(s)were tested separately as part of the annual monitor certification test. <br /> If the entire depth of the UDC is not tested. specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is`'NO"or'NA".the entire UDC must be tested. (See SWRCB LG-160) <br />