v/ <br />Page 5 of 9 <br />6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specif}) <br />Test Method Used: ❑ Pressure ❑ vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Level Change Indicator <br />Equipment Resolution: 0.0025 <br />Sump # 87 <br />Sump # 87 SYP <br />Sump # 91 <br />Sump # Vent Box <br />Sump Diameter: <br />42 in <br />42 in <br />42 in <br />Sump Depth: <br />36 in <br />33 in <br />31 in <br />24 in <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />15 in <br />17 in <br />14 in <br />18 in <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />13 in <br />14 in <br />11 in <br />12 in <br />Condition of sump prior to testing: <br />Dry <br />Dry <br />Dry <br />Dry <br />Portion of Sump Tested' <br />2" above prod. piping <br />2" above prod. piping <br />2" above prod. piping <br />2" above prod. piping <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?' <br />❑Yes ❑No ®NA <br />❑Yes [:]No ®NA <br />❑Yes [:]No ®NA <br />❑Yes ❑No ❑NA <br />Turbine shutdown response time <br />* See comments <br />See comments <br />See comments <br />See comments <br />Is system programmed for fail-safe <br />[:]Yesshutdown? Yes [:]No ®NA <br />❑Yes [:]No ®NA <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />Was fail-safe verified to be <br />operational? <br />Yes No ®NA <br />❑ ❑ <br />❑ Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />5 min <br />5 min <br />5 min <br />5 min <br />Test Start Time: <br />10:50 AM <br />10:35 AM <br />10:25 AM <br />10:00 AM <br />InitialReading (R,): <br />0 <br />0 <br />0 <br />0 <br />Test End Time: <br />11:20 AM <br />11:05 AM <br />10:55 AM <br />10:30 AM <br />Final Reading (RF): <br />0 <br />0 <br />0 <br />0 <br />Test Duration: <br />30 min <br />30 min <br />30 min <br />30 min <br />Change in Reading (RF -R,): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />0.0025 <br />0.0025 <br />0.0025 <br />0.0025 <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail' <br />Was sensor removed for testing? <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes ❑No RNA <br />®Yes ❑No ❑NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />" Sump(s) sensor(s) were tested separately as part of the annual monitor certification test. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -I60) <br />