Laserfiche WebLink
HAZARDOUS MATERIAL <br />MANAGEMENT PLAN & UST MONITORIO PLAN <br />DEALER: Keith B. Geist OWNER: CHEVRON, U.S.A. <br />BUSINESS NAME: Keith Geist Chevron P.O.BOX 5004 <br />STREET: 25650 Hwy 99, North SAN RAMON, CA 94583-0804 <br />CITY: Acampo , CA ZIP: 95220 <br />STATION No: 8050.20 <br />SITE PHONE # 209-333-1135 <br />DUNN & BRADSTREET # 00-914-0559 SIC CODE: 5541 7538 <br />NATURE OF BUSINESS: <br />GASOLINE SALES X AUTO REPAIR CAR WASH FOOD MART X <br />EXISTING UNDERGROUND TANKS ARE AS FOLLOWS: <br />No. of SIZE MATERIAL CONST SPILL OVERFILL <br />TANKS (gal) (STL/FG) (SW/DW) (Y/N) (Y/N) <br />SUPER UNLEADED 1 12,000 FG DW Y Y <br />REGULAR UNLEADED 1 12,000 FG DW Y Y <br />PLUS UNLEADED 1 12,000 FG DW Y Y <br />DIESEL 0 <br />WASTE OIL 0 <br />PRODUCT LINES: MATERIAL: FG <br />CONSTRUCTION: DOUBLE WALL <br />LINE LEAK DETECTION METHOD: X ELECTRONIC MECHANICAL <br />All product lines have line leak detectors capable of detecting a leak of <br />3 gallons or more per hour at 10 lbs. per square inch line pressure <br />within 1 hour; see page one for a description of the equipment installed <br />at this location. <br />All product lines are pressurized using a submerged pumping system and <br />are tested annually to assure the leak detectors are functional.Impact <br />valves are also inspected annually to assure closure. <br />Repair and/or replacement of all leak detectors and impact valves will be <br />done annually at the time of inspection and retested to meet the above <br />test conditions. <br />* This document is to be kept current and at the site. Revision 8, 1991 <br />1 <br />