Laserfiche WebLink
I <br />0 41 <br />high product level <br />low product level <br />high water level (at tank bottom) <br />111-11 .11114 11*611 Eell 10 4011JUM1 <br />a) The system is capable of performing precision tank tests to the highest <br />value, frequency and reliability as specified by U.S. EPA regulations and <br />applicable Local Codes (whichever is more stringent). It also has third <br />party certification. <br />b) Display of the date, time, and product level of the last successful test <br />for each tank for the following tests: <br />Annual Precision Test (e.g., 0.1 gph leak rate) <br />Monthly Precision Test (e.g., 0.2 gph leak rate) <br />• •• . • <br />Attempt a precision test every night during a defined period of time <br />with the ability to abort and restart the test, during and after a pump <br />cycle. <br />o Capability to perform leak testing at the command of the operator. <br />The system will wait for a prescribed period of time after a product <br />delivery and pumping cycle prior to starting a tank test or water <br />withdrawal. <br />Monthly Tank Test Required <br />Failed Monthly Tank Test <br />Loss of Product <br />(25 days since last achieved) <br />(e.g., 0.2 gph leak rate) <br />(unexpected drop in product level) <br />Nelms F-079110- I&= NMB= <br />° pump running <br />° line pressure (reading 0.1 psi increments) <br />° line is in test <br />011 •• r • • - <br />° Pump Failure (i.e., pump on but not requested, or <br />pump off during request) <br />..- <br />