Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32262 2360 GRANTLINE I-205 OFF RAMP TRACY CA.95376 <br /> Work Order#: 2222223 Date: 05/15/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ft"3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volum Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (f A3) AIL Average Pass/Fail <br /> 7.508 47.88 9.4 2926.72 2927.74 1.020 1.02 <br /> 2 opw 27r PLUS 1.02 Pass <br /> 7.494 50.68 8.9 2927.74 2928.74 1.000 1.00 <br /> 3 opw 27r REG 1.00 Pass <br /> 7.534 51.72 8.7 2928.74 2929.76 1.020 1.01 <br /> 3 opw 27r PREMIUM 1.01 Pass <br /> 7.505 51.81 8.7 2929.76 2930.77 1.010 1.01 <br /> 3 opw 27r PLUS 1.01 Pass <br /> 7.490 49.12 9.1 2930.77 2931.87 1.100 1.10 <br /> 4 opw 27r REG 1.10 Pass <br /> Type of System Tested: Gilbarco Vapory <br />