Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32262 2360 GRANTLINE I-205 OFF RAMP TRACY CA.95376 <br /> Work Order#: 2222223 Date: 05/15/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ft"3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volum Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft-3) A/L Average Pass/Fail <br /> 7.493 49.09 9.2 2931.87 2932.98 1.110 1.11 <br /> 4 opw 27r PREMIUM 1.11 Pass <br /> 7.504 47.53 9.5 2932.98 2934.08 1.100 1.10 <br /> 4 opw 27r PLUS 1.10 Pass <br /> 7.491 54.33 8.3 2934.08 2935.16 1.080 1.08 <br /> 5 opw 27r REG 1.08 Pass <br /> 7.498 51.25 8.8 2935.16 2936.23 1.070 1.07 <br /> 5 opw 27r PREMIUM 1.07 Pass <br /> 7.513 46.75 9.6 2936.23 2937.28 1.050 1.05 <br /> 5 opw 27r PLUS 1.05 Pass <br /> Type of System Tested: Gilbarco Vapory <br />