Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32262 2360 GRANTLINE I-205 OFF RAMP TRACY CA.95376 <br /> Work Order#: 2222223 Date: 05/15/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(f A3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volume Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft^3) A/L Average Pass/Fail <br /> 7.496 54.62 8.2 2937.28 2938.35 1.070 1.07 <br /> 6 opw 27r REG 1.07 Pass <br /> 7.505 49.47 9.1 2938.35 2939.39 1.040 1.04 <br /> 6 opw 27r PREMIUM 1.04 Pass <br /> 7.495 47.72 9.4 2939.39 2940.45 1.060 1.06 <br /> 6 opw 27r PLUS 1.06 Pass <br /> 7.511 52.37 8.6 2940.45 2941.55 1.100 1.10 <br /> 7 opw 27r REG 1.10 Pass <br /> 7.501 53.50 8.4 2941.55 1 2942.66 1.110 1.11 <br /> 7 opw 27r PREMIUM 1.11 Pass <br /> Type of System Tested: Gilbarco Vapory <br />