Liquid level gauge/leak detection system,designated 8601.Associated Apparatus,non-hazardous location, liquid level gauge/leak
<br /> detector control unit, Form No. 86019X-XXX,where X represents any alphanumeric character. Provides intrinsically safe circuits for use in Class I,
<br /> Division 1,Group D,and Class I,Zone 0,Group IIA Hazardous Locations; may be used with up to 12 intrinsically safe probes/sensors when
<br /> installed in accordance with Control Drawing 331940-018.Suitable Intrinsically Safe Devices for use in Class I,Div. 1,Group D are 2 to 1
<br /> Sensor Input Box-Form No. 857390-102 only for use with Sump,Position Sensitive and Hydrostatic Sensors, Form No.794380 followed
<br /> by-208,-209, -301, -304,-323;or Magnetostrictive probes, Form No.84639,followed by 0 to 9,followed by 0 to 9,followed by 00 to 99 or
<br /> Form No. 85639,followed by 0 or 1,followed by 0 to 9,followed by 00 to 99 or Form No. 857080or Form No. 846291,followed by-100 through-
<br /> 199 or ISD Flow Meter Form No.331847-001,331847-002,332374-001 or 332374-002 or ISD Pressure Sensor Form No. 86119X-XXX or
<br /> Digital pressure line leak, Form No. 332681-XXX; or Discriminating dispenser pan,containment pump,interstitial sump,hydrostatic
<br /> and position sensitive sensors,Form No. 794380 followed by-208,-209,-301,-302,-303-304,-322, -323, -333,-343,-344,-345,-352, -
<br /> 430 or Form Nos.794390,followed by-401,-404,-407, -409,-420,-449,-460; or CSTP Liquid Switch,UL Listed Veeder-Root Submersible
<br /> Pump Basic Models PC or PAGC; or Vapor sensor,Form No. 794390-700 or Solid state discriminating sensors,Form No. 794380,followed by-
<br /> 320,-350,-360,-361,-362; or Solid state dispenser pan and containment sump sensors, Form No. 794380,followed by-321,-351; or
<br /> Ground water sensors, Form No.794380,followed by-621,-622,-624; or Vacuum Sensor, Form No. 332175-XXX; or Oil Water Separator Sensors
<br /> -Form Nos. 794690 followed by-000 to-999; or Mag Plusi.The control unit may also be provided with the following equipment for use in non-
<br /> hazardous locations: Overfill alarm,Form No. 790091-001,with or without an acknowledgement switch Form No. 790095-001 or
<br /> Communication Modules,Form Nos. 865090-301, -302,-303,-304,-330,-331, -332,-333, -339, -340,-341 or-401 may be used with
<br /> peripheral equipment as specified in the installation Instructions.
<br /> Liquid level gauge/leak detection system,designated 8603.Associated Apparatus,non-hazardous location,liquid level gauge/leak
<br /> detector control unit, Form No.86039X-XXX,where X represents any alphanumeric character. Provides intrinsically safe circuits for use in Class I,
<br /> Division 1,Group D Hazardous Locations; may be used with up to 16 intrinsically safe probes/sensors per USM Module when installed in
<br /> accordance with Control Drawing 331940-019.Suitable Intrinsically Safe Devices,for use in Class I, Division 1,Group D are 2 to 1 Sensor
<br /> Input Box-Form No.857390-102 only for use with Sump,Position Sensitive and Hydrostatic Sensors, Form Nos.794380 followed by-208,
<br /> -209, -301, -304,-323,-333; or Magnetostrictive Probes-Form No. 84639 followed by 0 to 9,followed by 0 to 9,followed by 00 to 99 or Form
<br /> No.85639,followed by 0 or 1,followed by 0 to 9,followed by 00 to 99,or Form No. 857080,or Form No. 846291 followed by-100 through-199;
<br /> or Discriminating Dispenser Pan,Containment Pump,Interstitial Sump,Hydrostatic and Position Sensitive Sensors-Form Nos.
<br /> 794380 followed by-208, -209,-301,-303-304,-322,-323, -333, -343,-344,-345,-352,-430 or Form Nos. 794390 followed by-401, -404,-
<br /> 407,-409,-420,-460; or CSTP Liquid Switch,UL Listed Veeder-Root Submersible Pump Basic Models PC or PAGC; or Vapor Sensor-Form No.
<br /> 794390-700;or Solid State Discriminating Sensors-Form Nos.794380 followed by-320,-350,-360,-361,-362;or Solid State Dispenser
<br /> Pan and Containment Sump Sensors-Form Nos.794380 followed by-321,-351; or Ground Water Sensors-Form No.794380 followed by-
<br /> 621,-622,-624; or Vacuum Sensor,Form No. 332175-XXX;or Oil Water Separator Sensors-Form Nos. 794690 followed by-000 to-999; or
<br /> Digital Pressure Line Leak-Form No. 85908X-XXX; or Mag Plus1.The control unit may also be provided with the following equipment for use
<br /> in non-hazardous locations: Overfill alarm,Form No.790091-001,with or without an acknowledgement switch Form No.790095-001; or USM
<br /> Modules, Form No. 865090-100,-101,-102,-103 or-104,up to four provided,module provides intrinsically safe circuits for combinations
<br /> described above or I/O Modules, Form No. 865090-200, -210, -211, -212,-220,-221,or-222,up to four provided.
<br /> Class I,Division 1,Group D and Class I,Zone O,AEx Is IIA T4 Hazardous Locations.
<br /> Liquid level probes, intrinsically safe for use in Class I,Div. 1,Group D and Class I Zone 0 Group IIA; hazardous locations when installed in
<br /> accordance with installation manual 577013-744,Form Nos.84539,84639,84629,85639 or 84739 followed by 0 or 1,followed by-XXX,where X
<br /> is any character not related to certification.
<br /> Liquid level probes, intrinsically safe for use In Class I, Div. 1,Group D and Class I Zone 0 Group IIA; hazardous locations when installed in
<br /> accordance with installation manual 577013-812,Form Nos. 85708 followed by 0 or 1,followed by-XXX,where X is any character not related to
<br /> certification.
<br /> Vacuum Sensor,intrinsically safe for use in Class I, Div. 1,Group D and Class I Zone 0 Group IIA; hazardous locations when installed in
<br /> accordance with installation manual 577013-836,Form No. 332175-XXX.
<br /> ISD Pressure Sensor,Part No. 86119X-XXX where X may be any character,intrinsically safe device for use in Class I, Div. 1,Group D and Class
<br /> I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 577014-019. May be provided with installation Kits Nos.
<br /> 330020-515,-715 and/or-716 as described in the manual.
<br /> Steel tank sensors, Form Nos. 7943XX-4X0;where X may be any character, intrinsically safe device for use in Class 1, Div. 1,Group D and Class
<br /> I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 576013-616.
<br /> Single point hydrostatic sensors, Form Nos. 79438X-304;where X may be any character,intrinsically safe device for use in Class I,Div. 1,
<br /> Group D and Class I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 577013-838.
<br /> Hydrostatic sensors,Form Nos. 7943XX-30X; where X may be any character,intrinsically safe device for use in Class 1, Div. 1,Group D and
<br /> Class I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 576013-795.
<br /> Sump sensors,Form Nos. 7943XX-20X;where X may be any character,intrinsically safe device for use in Class I, Div. 1,Group D and Class I
<br /> Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 576013-301.
<br /> Vapor sensors,Farm Nos. 7943XX-70X;where X may be any character,intrinsically safe device for use in Class I, Div. 1,Group D and Class I
<br /> Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 576013-607.
<br /> Ground water sensors,Form Nos. 7943XX-62X;where X may be any character,intrinsically safe device for use in Class I,Div. 1,Group D and
<br /> Class I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 576013-763.
<br /> Position sensitive sensor, Form No. 7943XX-323; where X may be any character, Intrinsically safe device for use in Class I, Div. 1,Group D and
<br /> Class I Zone 0 Group IIA; Hazardous Locations when installed in accordance with manual 577013-809.
<br />
|