Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> COUNTY <br /> — <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> FLYING J TRAVEL PLAZA#fi17 1 15237 N Thornton Rd Lodi Aril 23 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 201 CCR 2712(b) Failure to maintain monitoring, maintenance, and follow up action records. <br /> Maintenance and monitoring records for the last three years were not found on site. <br /> -The secondary containment test results for 87 Tank#4 from 10/6/17 were not found on site. <br /> These records shall be maintained on site for at least three years. Monitoring records include: (1) date and time of all <br /> monitoring or sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visual <br /> observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other <br /> monitoring equipment, ground water elevations, or other test results; (6) results of inventory readings and <br /> reconciliations. Immediately locate and maintain all missing test records for the last three years on site. <br /> This is a repeat violation, Class ll. <br /> 204 CCR 2712(1) Current monitoring plan approved by the EHD not found on site. <br /> A current, approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> This is a repeat violation, Class II. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to check and note all required items on the visual inspection reports. The incorrect <br /> and missing information included the following from the inspection reports: <br /> -Secondary containment testing was incorrectly marked as 'NA' but a current, correct test date was listed. <br /> -The NA answers were not documented in Section I II. <br /> -Section V of the reports was completed as a duplicate of Section III and did not include the corrections taken by the <br /> facility. <br /> During the visual inspection, the designated operator shall check that all required testing and maintenance for the <br /> UST system have been completed and shall check all required items on the report. Ensure that designated <br /> operators performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 301 HSC 25292.1(a) UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the UDC. The <br /> underground storage tank system shall be operated to prevent unauthorized releases. Immediately provide approved <br /> secondary containment for the filters under permit and inspection by the EHD. <br /> This is a Class II violation. <br /> FA0012979 PRO517272 SCO01 04/23/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 Of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />